Troubleshooting diagram 17 – IDEC MicroSmart Pentra User Manual

Page 150

Advertising
background image

13: T

ROUBLESHOOTING

13-24

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

Troubleshooting Diagram 17

NO

Did you make sure of

source 1 device of the RXD

instruction?

Are communication

parameters set correctly

using WindLDR?

Are inputs to more

than 5 RXD instructions

on simultaneously?

Data is not received correctly in the
user communication mode.

Set the communication parameters to
match those of the remote terminal
using WindLDR. Web server CPU
module can use constants only for start
and stop delimiters. See “Programming
WindLDR” of the basic volume (page
10-5.)

Is the data register

designated as receive status

used repeatedly?

Correct the program to replace the
duplicate data register with a different
data register.

Is a start delimiter specified in

the RXD instruction?

Did you check the start

delimiter of incoming data?

Did you check the

format of incoming

data?

Is an end delimiter specified in

the RXD instruction?

Did you check the end

delimiter of incoming data?

Is the receive timeout

value set correctly using

WindLDR?

Is one input used to start

multiple RXD instructions?

Make sure that the receive format of
the RXD instruction matches that of
the incoming data.

Correct the program to make sure
that inputs to more than 5 RXD
instructions do not go on
simultaneously.

Use one input to start one RXD
instruction without a start delimiter.

Make sure that the start delimiter in
the RXD instruction matches that of
the incoming data.

Make sure that the end delimiter in
the RXD instruction matches that of
the incoming data.

Make sure that the receive timeout
value is larger than character intervals
of the incoming data.

Make sure that the receive data
designated as the source 1 device is
correct.

YES

YES

YES

YES

NO

NO

NO

NO

YES

YES

YES

NO

NO

NO

YES

NO

NO

YES

YES

NO

Call IDEC for assistance.