Error causes and actions -4 – IDEC MicroSmart Pentra User Manual

Page 130

Advertising
background image

13: T

ROUBLESHOOTING

13-4

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

CPU Module Operating Status, Output, and ERR LED during Errors

Note 1: When a program RAM sum check error occurs, operation is stopped momentarily for reloading the user program. After
completing the reloading, operation resumes.

Note 2: Operation starts to run and outputs are turned on or off according to the user program as default, but it is also possible to stop
operation and turn off outputs using the Function Area Settings on WindLDR. See "Run/Stop Selection at Memory Backup Error" of the
basic volume (page 5-3).

Note 3: Memory cartridge program transfer error bit is available on FC5A-D12K1E and FC5A-D12S1E only.

Error Causes and Actions

0001h: Power Failure

This error indicates when the power supply is lower than the specified voltage. This error is also recorded when the
power is turned off. Clear the error code using the HMI module or WindLDR on a computer.

0002h: Watchdog Timer Error

The watchdog timer monitors the time required for one program cycle (scan time). When the time exceeds 400 ms, the
watchdog timer indicates an error. Clear the error code using the HMI module or WindLDR on a computer. If 400 ms is
too small, the watchdog timer value can be increased in the Function Area Settings. For details, see “Watchdog Timer
Setting” on page 5-3

.

If this error occurs frequently, the Web server CPU module has to be replaced.

0004h: Data Link Connection Error

This error indicates that the Function Area Settings for data link communication are incorrect or the cable is not
connected correctly. Make sure that slave stations are set to station numbers 1 through 31 using WindLDR. No
duplication of station numbers is allowed. See "Programming WindLDR" of the basic volume (page 11-8)

.

To correct this error, make corrections in the Function Area Settings and download the user program to each station, or
connect the cable correctly. Turn power off and on again for the slave station. Then take one of the following actions:

• Turn power off and on for the master station.

• Initialize data link communication for the master station using WindLDR on a computer. See "Operating Procedure for Data Link

System" of the basic volume (page 11-12).

• Turn on special internal relay M8007 (data link communication initialize flag) at the master station. See "Special Internal Relays

for Data Link Communication" of the basic volume (page 11-7).

0008h: User Program ROM Sum Check Error

The user program stored in the Web server CPU module EEPROM is broken. Download a correct user program to the
Web server CPU module, and clear the error code using the HMI module or WindLDR on a computer.

Error Items

Operating

Status

Output

ERR LED

Checked at

Power failure

Stop

OFF

OFF

Any time

Watchdog timer error

Stop

OFF

ON

Any time

Data link connection error

Stop

OFF

OFF

Initializing data link

User program ROM sum check error

Stop

OFF

ON

Starting operation

TIM/CNT preset value sum check error

Maintained

Maintained

OFF

Starting operation

User program RAM sum check error

Stop (Note 1)

OFF

ON

During operation

Keep data error

Maintained/

Stop (Note 2)

Maintained/OFF

(Note2)

OFF

Turning power on

User program syntax error

Stop

OFF

ON

Downloading user program

User program writing error

Stop

OFF

ON

Downloading user program

CPU module error

Stop

OFF

ON

Turning power on

Clock IC error

Maintained

Maintained

ON

Any time

Memory cartridge program transfer error
(Note 3)

Stop

OFF

ON

Turning power on

I/O bus initialize error

Stop

OFF

ON

Turning power on

User program execution error

Maintained

Maintained

ON

Executing user program