IDEC MicroSmart Pentra User Manual

Page 142

Advertising
background image

13: T

ROUBLESHOOTING

13-16

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

Troubleshooting Diagram 8

Troubleshooting Diagram 9

Is the scan time longer than

400 ms?

Change the watchdog timer value in the
Function Area Settings. For details, see
“Watchdog Timer Setting” on page 5-3.

Watchdog timer error occurs
and the CPU does not run.

Call IDEC for assistance.

YES

NO

Are the input ON/OFF

voltage levels correct?

The interrupt/catch input
cannot receive short pulses.

Make sure of correct input voltage.
ON voltage:

15V DC minimum

OFF voltage:

5V DC maximum

YES

NO

Call IDEC for assistance.

END