Troubleshooting diagram 11 – IDEC MicroSmart Pentra User Manual

Page 144

Advertising
background image

13: T

ROUBLESHOOTING

13-18

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

Troubleshooting Diagram 11

Is the ERR LED on?

Is “Calendar/clock error”

displayed?

The calendar/clock does not
operate correctly.

See Troubleshooting Diagram 3,
“The ERR LED is on.”

Read the error data using WindLDR. See
“Reading Error Data” on page 13-2.

Is the calendar/clock

operating normally?

Clear the error code. See “Clearing Error Codes from WindLDR”
on page 13-2.
The clock data is broken. Set the calendar/clock using WindLDR.
See "Setting Calendar/Clock Using WindLDR" of the advanced
volume (page 9-6).
Adjust the clock cartridge accuracy. See "Adjusting Clock
Cartridge Accuracy" of the advanced volume (page 9-8).

Monitor the PLC status using WindLDR.

Is the clock cartridge

installed correctly?

Install the clock cartridge correctly. See "Clock
Cartridge" of the basic volume (page 2-95).

END

Call IDEC for assistance.

YES

NO

YES

NO

NO

YES

YES

NO