Troubleshooting Diagram 7

Does the monitored input

turn on and off?

Monitor the designated stop or reset
input using WindLDR on a computer.

Is the designated stop or

reset input on?

Is M8000 off?

Turn on the designated input.

The input circuit in the CPU module is
damaged.
Replace the CPU module.

Is stop or reset input

designated in the WindLDR

Function Area Settings?

Monitor the start control special
internal relay M8000 using WindLDR
on a computer.

Turn off the start control special
internal relay M8000 using WindLDR
on a computer.

Cannot stop or reset operation.

Note: To monitor M8000, from the WindLDR menu bar,
select Online > Monitor > Monitor, then Online > Custom >
New Custom Monitor. Enter M8000 in the Device box in
the Custom Monitor dialog box.

Note: To turn off M8000, enter 0 in the Current Value box in
the Custom Monitor dialog box.

Call IDEC for assistance.

YES

YES

YES

YES

NO

NO

NO

NO