Function specifications -5 – IDEC MicroSmart Pentra User Manual

Page 21

Advertising
background image

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

2-5

2: M

ODULE

S

PECIFICATIONS

Function Specifications

CPU Module Specifications

CPU Module

FC5A-D12K1E

FC5A-D12S1E

Program Capacity

62,400/127,800 bytes (10,400/21,300 steps) (Note 1)

Expandable I/O Modules

7 modules + additional 8 modules using the expansion interface module

I/O Points

Input

8

Expansion: 224

(Note 2)

Additional: 256

(Note 3)

Output

4

User Program Storage

FROM (10,000 rewriting life)

RAM Backup

Backup Duration

Approx. 30 days (typical) at 25°C after backup battery fully charged

Backup Data

Internal relay, shift register, counter, data register, expansion data register

Battery

Lithium secondary battery

Charging Time

Approx. 15 hours for charging from 0% to 90% of full charge

Battery Life

5 years in cycles of 9-hour charging and 15-hour discharging

Replaceability

Not possible to replace battery

Control System

Stored program system

Instruction Words

42 basic
152 advanced

Processing Time

Basic instruction

83 µs (1000 steps) See "Execution Times for Instructions" of the basic volume (page A-1).

END processing

0.35 ms (not including expansion I/O service, clock function processing, data link
processing, interrupt processing, USB communication processing, and Ethernet
communication processing) See "Breakdown of END Processing Time" of the basic
volume (page A-5).

Internal Relay

2,048

Shift Register

256

Timer

256 (1-sec, 100-ms, 10-ms, 1-ms)

Counter

256 (adding, dual pulse reversible, up/down selection reversible)

Data Register

2,000

Expansion Data Register

6,000

Extra Data Register

40,000

Input Filter

Without filter, 3 to 15 ms (selectable in increments of 1 ms)

Catch Input
Interrupt Input

Four inputs (I2 through I5) can be designated as catch inputs or interrupt inputs
I2 and I5:

I3 and I4:

Minimum turn on pulse width: 40 µs maximum
Minimum turn off pulse width: 150 µs maximum
Minimum turn on pulse width: 5 µs maximum
Minimum turn off pulse width: 5 µs maximum

Self-diagnostic Function

Power failure, watchdog timer, data link connection, user program sum check (FROM,
external EEPROM), timer/counter preset value sum check, user program RAM sum
check, keep data, user program syntax, user program writing, CPU module, clock IC, I/O
bus initialize, user program execution, memory cartridge program transfer

Start/Stop Method

Turning power on and off
Start/stop command in WindLDR
Turning start control special internal relay M8000 on and off
Turning designated stop or reset input off and on

High-speed Counter

Total 4 points

Single/two-phase selectable:

100 kHz (2 points)

Single-phase:

100 kHz (2 points)

Counting range:

0 to 4,294,967,295 (32 bits)

Operation mode:

Rotary encoder mode and adding counter
mode

Analog Potentiometer

1 point

Data range:

0 to 255

Advertising