General Specifications

Normal Operating Conditions

Power Supply

Note 1: Among relay output modules connected to the CPU module, a maximum of 54 points can be turned on simultaneously. Among
relay outputs connected beyond the expansion module, a maximum of 54 points can be turned on simultaneously. Relay outputs
exceeding these limits may not turn on correctly.

Note 2: Maximum power consumption for individual CPU module is 3.0W (125 mA at 24V DC).

CPU Module

FC5A-D12K1E

FC5A-D12S1E

Operating Temperature

0 to 55°C (operating ambient temperature)

Storage Temperature

–25 to +70°C

Relative Humidity

10 to 95% (non-condensing, operating and storage humidity)

Pollution Degree

2 (IEC 60664-1)

Degree of Protection

IP20 (IEC 60529)

Corrosion Immunity

Atmosphere free from corrosive gases

Altitude

Operation:

0 to 2,000m (0 to 6,565 feet)

Transport:

0 to 3,000m (0 to 9,840 feet)

Vibration Resistance

When mounted on a DIN rail or panel surface:
5 to 8.4 Hz amplitude 3.5 mm, 8.4 to 150 Hz acceleration 9.8 m/s

2

(1G)

2 hours per axis on each of three mutually perpendicular axes (IEC 61131-2)

Shock Resistance

147 m/s

2

(15G), 11 ms duration, 3 shocks per axis on three mutually perpendicular axes

(IEC 61131-2)

ESD Immunity

Contact discharge: ±4 kV, Air discharge: ±8 kV (IEC 61000-4-2)

Weight

200g

Rated Power Voltage

24V DC

Allowable Voltage Range

20.4 to 26.4V DC (including ripple)

Maximum Input Current

700 mA (26.4V DC)

Maximum Power Consumption
(Note 1, 2)

CPU module + 7 I/O modules + expansion module + 8 I/O modules
19W (26.4V DC)

Allowable Momentary Power
Interruption

10 ms (at 24V DC)

Dielectric Strength

Between power and

terminals:

Between I/O and

terminals:

500V AC, 1 minute
500V AC, 1 minute

Insulation Resistance

Between power and

terminals:

Between I/O and

terminals:

10 M

Ω minimum (500V DC megger)

10 M

Ω minimum (500V DC megger)

Noise Resistance

DC power terminals:
I/O terminals (coupling clamp):

1.0 kV, 50 ns to 1 µs
1.5 kV, 50 ns to 1 µs

Inrush Current

50A maximum (24V DC)

Grounding Wire

UL1015 AWG22, UL1007 AWG18

Power Supply Wire

UL1015 AWG22, UL1007 AWG18

Effect of Improper Power Supply
Connection

Reverse polarity:
Improper voltage or frequency:
Improper lead connection:

No operation, no damage
Permanent damage may be caused
Permanent damage may be caused