13: T

ROUBLESHOOTING

13-20

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

Troubleshooting Diagram 13

Turn off the power to the master station, and turn on the
power after a few seconds.

Is the error code 0

at all stations?

Is the communication

cable connected to the

RS485 port correctly?

Make sure of correct wiring. See "Data Link System Setup" of
the basic volume (page 11-2).

Turn off M8006 using WindLDR.

Check error codes for the troubled stations.
See "Data Link Communication Error Code"
of the basic volume (page 11-5).

For the master station, click the Initialize
Data Link button (see "Operating
Procedure for Data Link System" of the
basic volume (page 11-12)) or turn on
M8007 during operation using
WindLDR.

Are error codes

cleared to 0 at all

stations?

Clear the error codes at all stations using WindLDR. See
“Clearing Error Codes from WindLDR” on page 13-2.

Data link communication is impossible.

M8006: Data link communication prohibit flag
M8007: Data link communication initialize flag

Is data link selected for

port 2 correctly?

Is the PWR LED on?

See Troubleshooting Diagram 1,
“The PWR LED does not go on.”

Is M8006 on at the

master station?

Check port 2 settings using WindLDR.

See "Programming WindLDR" of the

basic volume (page 11-8).

Select data link for port 2 correctly and download the
user program again. See "Programming WindLDR" of
the basic volume (page 11-8).

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Call IDEC for assistance.

END