Troubleshooting diagram 15 – IDEC MicroSmart Pentra User Manual

Page 148

Advertising
background image

13: T

ROUBLESHOOTING

13-22

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

Troubleshooting Diagram 15

Did you make sure of

source 1 device of the TXD

instruction?

Are communication

parameters set correctly

using WindLDR?

Are inputs to more than

5 TXD instructions on

simultaneously?

Correct the program to make sure that inputs to
more than 5 TXD instructions do not go on
simultaneously.

Data is not transmitted correctly
in the user communication mode.

Set the communication parameters to match those
of the remote terminal using WindLDR. See
"Programming WindLDR" of the basic volume
(page 10-5).

Make sure that the busy signal at the remote
terminal does not exceed 5 sec.

Is the data register designated

as transmit status used

repeatedly?

Correct the program to replace the duplicate data
register with a different data register.

Is duration of the busy

signal at the remote

terminal less than 5 sec?

Make sure that the transmit data designated as
source 1 device is correct.

When the user communication still has a problem after completing the above procedure, also
perform the procedure of Diagram 14 described on the preceding page.

Call IDEC for assistance.

YES

YES

NO

NO

NO

YES

NO

NO

YES

YES