Modbus TCP Server

When the Web server CPU module is configured as the Modbus TCP server, Modbus TCP client devices can access and
communicate with the Web server CPU module.

When the Web server CPU module receives a valid request from a Modbus TCP client device, the data is read or written
according to the request received. The communication data received from Modbus TCP clients are processed at the END
processing.

Modbus TCP Server Specifications

*1: When timeout occurs, the MicroSmart discards the received data and waits for the first frame of the next valid communication.

*2: The value when all server connections are configured as Modbus TCP server is indicated.

Address Map

*1: Addresses generally used for Modbus communication. For details about the calculation method of Modbus addresses for

MicroSmart devices, see chapter 12 of FC5A user’s manual basic volume.

Parameter

Modbus TCP Server

Slave Number

Ignored

Response Time

1.5 ms

Receive Timeout *1

500 ms

Number of Clients that can Access Simultaneously *2

8 maximum

Port Number

502 (can be changed between 0 and 65535)

Supported Function Code

01 Read Coil Status
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
05 Force Single Coil
06 Preset Single Register
15 Force Multiple oils
16 Preset Multiple Registers

Modbus Device

Name

Modbus Address
Map (Decimal)

*1

Communication

Frame Address

MicroSmart Device

Applicable

Function Code

Coil
(000000 and above)

000001 - 000504

0000 - 01F7

Q0 - Q627

1, 5, 15

000701 - 000956

02BC - 03BB

R0 - R255

001001 - 003048

03E8 - 07F7

M0 - M2557

009001 - 009256

2328 - 2427

M8000 - M8317

Input Relay
(100000 and above)

100001 - 100504

0000 - 01F7

I0 - I627

2

101001 - 101256

03E8 - 04E7

T0 - T255 (timer contact)

101501 - 101756

05DC - 06DB

C0 - C255 (counter contact)

Input Register
(300000 and above)

300001 - 300256

0000 - 00FF

T0 - T255 (timer current value)

4

300501 - 300756

01F4 - 02F3

C0 - C255 (counter current value)

Holding Register
(400000 and above)

400001 - 408000

0000 - 1F3F

D0 - D7999

3, 6, 16

408001 - 408500

1F40 - 2133

D8000 - D8499

409001 - 409256

2328 - 2427

T0 - T255 (timer preset value)

3

409501 - 409756

251C - 261B

C0 - C255 (counter preset value)

410001 - 450000

2710 -C34F

D10000 - D49999

3, 6, 16