W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

2-7

2: M

ODULE

S

PECIFICATIONS

Memory Cartridge (Option)

Note 1: User Web data is not stored.

Clock Cartridge (Option)

Communication Function

Note 1: Maximum baud rate when using data link communication is 57,600 bps.

Note 2: 1:1 Modbus communication only

Note 3: For special cables, refer to the Basic Volume Appendix “Cables” (page A-12).

Note 4: Recommended cable for RS485: Twisted-pair shielded cable with a minimum core wire of 0.3 mm

2

.

Conductor resistance 85

Ω/km maximum, shield resistance 20 Ω/km maximum.

Memory Type

EEPROM

Accessible Memory Capacity

32 KB, 64 KB, 128 KB
The maximum program capacity depends on the CPU module.
When using the 32 KB memory cartridge on the slim type CPU module, the maximum
program capacity is limited to 30,000 bytes.

Hardware for Storing Data

CPU module

Software for Storing Data

WindLDR

Quantity of Stored Programs

One user program can be stored on one memory cartridge. (Note 1)

Program Execution Priority

When a memory cartridge is installed, the user program on the memory cartridge is
executed.
User programs can be downloaded from the memory cartridge to the CPU module.
User programs can also be uploaded to the memory cartridge from the CPU module.

Accuracy

±30 sec/month (typical) at 25°C

Backup Duration

Approx. 30 days (typical) at 25°C after backup battery fully charged

Battery

Lithium secondary battery

Charging Time

Approx. 10 hours for charging from 0% to 90% of full charge

Battery Life

Approx. 100 recharge cycles after discharging down to 10% of full charge

Replaceability

Not possible to replace battery

Communication Port

Port 2

Communication Adapter

FC4A-PC1

FC4A-PC2

FC4A-PC3

Communication Module

FC4A-HPC1

FC4A-HPC2

FC4A-HPC3

Standards

EIA RS232C

EIA RS485

EIA RS485

Maximum Baud Rate

115,200 bps

115,200 bps

115,200 bps

Maintenance Communication
(Computer Link)

Possible

Possible

Possible

User Communication

Possible

Possible

Possible

Modem Communication

Data Link Communication

Possible
(31 slaves max.) (Note 1)

Possible
(31 slaves max.) (Note 1)

Modbus Communication

Possible (Note 2)

Possible

Possible

Maximum Cable Length

Special cable
(Note 3)

Special cable
(Note 3)

200m (Note 4)

Isolation between Internal Circuit
and Communication Port

Not isolated

Not isolated

Not isolated