<Appendix 2. Integrator (IT) Block>

A2-10

IM 01S01C01-01EN

Index

Parameter

Name

Initial

Value

Write

Mode

View

Definition

1 2 3 4

26

SRTOTAL

0.0

4

Indicates the snapshot of RTOTAL just before a reset.

27

SSP

0.0

4

Indicates the snapshot of TOTAL_SP just before a reset.

28

INTEG_TYPE

UP_

AUTO(1)

1 Integration Type Setting

Value

Name

Description

1

UP_AUTO Counts up and is automatically reset when

TOTAL_SP is reached.

2

UP_DEM

Counts up and is reset as demanded.

3

DN_AUTO Counts down and is automatically reset when

"0" is reached.

4

DN_DEM

Counts down and is reset as demanded.

5

PERIODIC Counts up and is reset at periods specified in

CLOCK_PER.

6

DEMAND

Counts up and is reset as demanded.

7

PER&DEM Reset periodically or as demanded.

29

INTEG_OPTS

0×0004

2 Specifies an integration optional function.

bit

Option Name

Description

0

Input 1 accumulate Selects Rate or Accum input of IN_1.

1

Input 2 accumulate Selects Rate or Accum input of IN_2.

2

Flow forward

Integrates forward flow (interprets

reverse flow as zero).*

3

Flow reverse

Integrates reverse flow (interprets

forward flow as zero).*

4

Use uncertain

Uses an input value of IN_1 or IN_2

whose status is "Uncertain" regarding it

as a value of "Good."

5

Use bad

Uses an input value of IN_1 or IN_2

whose status is "Bad" regarding it as a

value of "Good."

6

Carry

Carries over an excess exceeding the

threshold at reset to the next integration.

(Note that this does not apply to

UP_AUTO or DN_AUTO.)

7

Add zero if bad

Interprets an increment as zero if the

status of the increment is "Bad."

8

Confirm reset

After a reset, rejects the next reset until

"Confirm" is set to RESET_CONFIRM.

9

Generate reset

event

Generates an alert event at reset.

10 to

15

Reserved

* If both forward and reverse flows are enabled or disabled, both forward

and reverse flows are integrated.

30

CLOCK_PER

2.7[sec]

4

Specify the period at which a periodic reset is made.

31

PRE_TRIP

100000.0

4 Set an allowance applied before an integrated value exceeds the setpoint.

32

N_RESET

0.0

4

4

Indicates the number of resets in the range of 0 to 999999.

33

PCT_INCL

0.0[%]

4

4

The ratio of "the integrated values of the absolute values of the increments

whose status is Good" to the "integrated values of the absolute values of

the increments irrelevant to the status" (Equation).

34

GOOD_LIM

0.0[%]

4 The threshold value of the ratio of "the integrated values of the increments

whose status is Good" to all integrated values in which the status of OUT

is "Good".

35

UNCERT_LIM

0.0[%]

4 The threshold value of the ratio of "the integrated values of the increments

whose status is Good" to all the integrated values in which the status of

OUT is "Uncertain".

36

OP_CMD_INT

0

1

1

Operator command that resets integrated values.

37

OUTAGE_LIM

0.0

4 Maximum time for which values can be retained in the event of power

failure.

It does not effect the block operation.

38

RESET_

CONFIRM

0

2

2

Reset confirmation input, which is enabled when the Confirm reset option

of INTEG_OPTS is chosen