<7. Explanation of Basic Items>

7-4

IM 01S01C01-01EN

7.3.5 Indicator settings

To use the FVX110 as a field indicator, information

(Main Tag and Sub Tag) identifying field

instruments, units, bar graph scaling and other

parameters must be set to enable display on the

FVX110.

Selection of function block to receive output

signals from field instruments

(MAIN_CONNECT_YTPE, INxx_CONNECTION)

Select function block to receive output signals from

field instruments from MAO or IS function block.

Batch settings should start from the MAIN_

CONNECT_TYPE parameter in the LCD

transducer block. To use the MAO function block

to receive all 16 inputs, select 1: All connects to

MAO-FB, to use the IS function block, select 2:

All connects to ISEL-FB and to use a simulation

instruction for all inputs, select 3: All are in simulate.

To set a separate input source, start from the INxx_

CONNECTION parameter in the LCD transducer

block. To use the MAO function block to receive

inputs IN_01 to IN_08, set 1:from MAO-FB_1_INxx

(xx: 01~08). To use the IS function block to receive

the same inputs, set 2:from ISEL-FB_1_INxx (xx:

01~08). To use the MAO function block to receive

inputs from IN_09 to IN_16, set 1:from MAO-FB_

2_INxx (xx : 09~16). To use the IS function block

to receive the same inputs, set 2:from ISEL_FB_2_

INxx (xx : 09~16). Select 0:In simulate for all inputs

to perform a simulation instruction.

NOTE

Selecting 0: All are in simulate or 0: In simulate

will display directly input test input values for

IN_xx on the display.

Valid input values (VALID_CON_SUMMARY)

Select valid IN_xx (xx: 01~16) to indicate in LCD

at VALID_CON_SUMMARY. IN_xx which is not

chosen at VALID_CON_SUMMARY will not

indicated in LCD.

This setting is reflected to the MAO_CON_

SUMMARY, ISEL_CON_SUMMARY and the

SIM_CON_SUMMARY.

Main Tag settings (INxx_MAIN_TAG)

The Main Tag is a memo field for making settings

used for entering the most important information to

identify the indicating field instrument (for example,

a PD_TAG of field instrument). Setting can be done

in INxx_MAIN_TAG (xx: 01 to 16). Maximum of 32

characters can be set, but 14 characters are limit of

indication on LCD. Scroll to view the digits beyond

the first 14 digits. Use MAIN_TAG_SCROLL to set

the scroll Main Tag.

F0702.ai

Figure 7.2

Main Tag settings

NOTE

8 characters are allowed if page information

have set to enable. To set MAIN_TAG_

SCROLL=1:Active, it is possible to view

information exceeding the allowed number of

characters through scrolling.

Indicator setting (INxx_SCALE)

Use INxx_SCALE(xx:01 to 16) to set measuring

units, bar graph scaling and the number of decimal

point digits of display values. Scaling is normally

set to the same value as the field instrument

measurement range. Set the upper limit and lower

limit values in EU at 100% and EU at 0%. Scaling

is not a mandatory setting, but is required to enable

display of bar graphs.

F0703.ai

Figure 7.3 Indicator value settings

You can set the range of decimal places that are

displayed after the decimal point from 0 to 4 digits.

The number of decimal places is automatically

adjusted so that 5 digits are displayed.

Any measuring unit in the table of section 7.3.8 can

be selected. Here, (N) indicates “Normal” (normal

state) and (S) indicates “Standard” (standard state)

for standard mass flow rate.