<Appendix 4. Arithmetic (AR) Block>

A4-8

IM 01S01C01-01EN

Relative

Index

Index

AR1

Index

AR2

Parameter

Write

Mode

Valid

Range

Initial

Value

View

Description / Remarks

1 2 3 4

29

17529 17629 ARITH_

TYPE

1 to 10

0x01

1 Computation algorithm identification no.

Value Selection Name

Description

1

Flow

compensation,

linear

Flow compensation

(linear)

2

Flow

compensation,

square root

Flow compensation

(square root)

3

Flow

compensation,

approximate

Flow compensation

(approximate

expression)

4

BTU flow (*)

Quantity of heat

calculation

5

Traditional Multiply

Divide

Multiplication and

division

6

Average

Average calculation

7

Traditional summer Summation

8

Fourth order

Polynomial, Type 1

4th-order (auxiliary

input) polynomial

computation

9

HTG level

compensation (*)

HTG-level

compensation

10

Fourth order

Polynomial, Type 2

4th-order (main

input) polynomial

computation

* BTU stands for British thermal unit.

HTG stands for hydrostatic tank gauging.

30

17530 17630 BAL_TIME

More

than 0

0

4 Time taken to return to the set value.

31

17531 17631 BIAS

0

4 Bias value used to calculate the output.

32

17532 17632 GAIN

1

4 Gain value used to calculate the output.

33

17533 17633 OUT_HI_

LIM

+INF

4 Maximum output value.

34

17534 17634 OUT_LO_

LIM

-INF

4 Minimum output value.

35

17535 17635 UPDATE_

EVT

Indicates event information if an update event

(setting change) occurs.

36

17536 17636 BLOCK_

ALM

Indicates alarm information if a block alarm occurs.