<Appendix 4. Arithmetic (AR) Block>

A4-7

IM 01S01C01-01EN

Relative

Index

Index

AR1

Index

AR2

Parameter

Write

Mode

Valid

Range

Initial

Value

View

Description / Remarks

1 2 3 4

13

17513 17613 INPUT_

OPTS

0

2 Determines whether an input is used as a “good”

input when the input status is "bad" or “uncertain.”

Bit

Function

0

Handles IN as “good” input if its status

is “uncertain.”

1

Handles IN_LO as “good” input if its

status is “uncertain.”

2

Handles IN_1 as “good” input if its

status is “uncertain.”

3

Handles IN_1 as “good” input if its

status is “bad.”

4

Handles IN_2 as “good” input if its

status is “uncertain.”

5

Handles IN_2 as “good” input if its

status is “bad.”

6

Handles IN_3 as “good” input if its

status is “uncertain.”

7

Handles IN_3 as “good” input if its

status is “bad.”

8 to 15 Reserved

14

17514 17614 IN

0

5

Input block.

15

17515 17615 IN_LO

0

5

Input for a low-range indicator.

This is used for the RANGE EXTENSION

FUNCTION.

16

17516 17616 IN_1

0

5

Auxiliary input 1

17

17517 17617 IN_2

0

5

Auxiliary input 2

18

17518 17618 IN_3

0

5

Auxiliary input 3

19

17519 17619 RANGE_HI

0

4 High limit for switching to a high-range indicator by

the RANGE EXTENSION FUNCTION.

20

17520 17620 RANGE_LO

0

4 Low limit for switching to a low-range indicator by

the RANGE EXTENSION FUNCTION.

21

17521 17621 BIAS_IN_1

0

4 IN_1 bias

22

17522 17622 GAIN_IN_1

0

4 IN_1 gain

23

17523 17623 BIAS_IN_2

0

4 IN_2 bias

24

17524 17624 GAIN_IN_2

0

4 IN_2 gain

25

17525 17625 BIAS_IN_3

0

4 IN_3 bias

26

17526 17626 GAIN_IN_3

0

4 IN_3 gain

27

17527 17627 COMP_HI_

LIM

+INF

4 High limit of compensation factor f.

28

17528 17628 COMP_LO_

LIM

-INF

4 Low limit of compensation factor f.

Advertising