Yokogawa FVX110 User Manual

Page 21

Advertising
background image

<2. Handling Cautions>

2-11

IM 01S01C01-01EN

The criterion for such interconnection is that the

voltage (Ui), the current (Ii) and the power (Pi),

which intrinsically safe apparatus can receive,

must be equal or greater than the voltage (Uo),

the current (Io) and the power (Po) which can be

provided by the associated apparatus (supply unit).

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

In addition, the maximum unprotected residual

capacitance (Ci) and inductance (Li) of each

apparatus (other than the terminators) connected

to the fieldbus line must be equal or less than 5 nF

and 10 µH respectively.

Ci ≤ 5 nF, Li ≤ 10 µH

Supply unit
The supply unit must be certified by a Notified

body as FISCO model and following trapezoidal or

rectangular output characteristic is used.

Uo = 14...17.5 V (I.S. maximum value)

Io based on spark test result or other assessment,

No specification of Lo and Co is required on the

certificate or label.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

Loop resistance Rc: 15...150 Ω/km

Inductance per unit length Lc: 0.4...1 mH/km

Capacitance per unit length Cc: 45...200 nF/km

Length of spur cable: max. 60 m (IIC and IIB)

Length of trunk cable: max. 1 km (IIC) or 5 km

(IIB)

Terminators
The terminator must be certified by a Notified body

as FISCO model and at each end of the trunk

cable an approved line terminator with the following

parameters is suitable:

R = 90 . . . 102 Ω

C = 0 . . . 2.2 µF. (0.8...1.2 µF is required in

operation)

The resistor must be infallible according to IEC

60079-11.

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.

● Entity Model

Non-Hazardous

Locations

Hazardous Locations

F0210.ai

Terminator

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit and

Safety Barrier

Terminator

Data

U

U

I

I.S. fieldbus system complying with Entity model

I.S. values Power supply-field device:

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

Calculation of max. allowed cable length:

Ccable ≤ Co – ∑Ci – ∑Ci (Terminator)

Lcable ≤ Lo – ∑Li

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.

b. CENELEC ATEX (KEMA) Flameproof Type

Caution for CENELEC ATEX (KEMA)

flameproof type

Note 1. FVX110 Fieldbus Segment Indicator

with optional code /KF25 for potentially

explosive atmospheres:

• No. KEMA 10ATEX0157

• Applicable Standard:

EN 60079-0:2006, EN 60079-1:2004,

EN 61241-0:2006, EN 61241-1:2004

• Type of Protection and Marking Code:

Ex d IIC T6, Ex tD A21 IP6x T80

• Group: II

• Category: 2G, 2D

• Temperature Class: T6

• Enclosure: IP66 and IP67

• Ambient Temperature for gas-proof:

–50* to 75ºC (T6)

* –15ºC when O-ring material is Fluoro-rubber.

• Maximum Surface Temperature for dust-

proof:

T80ºC (Tamb.: –40* to 75ºC)

* –15ºC when O-ring material is Fluoro-rubber.

Advertising