<7. Explanation of Basic Items>

7-5

IM 01S01C01-01EN

NOTE

• When 5 digits are displayed, the values

beyond the decimal point are rounded off.

• When the sum of displayed digits and

decimal places is 5 or more digits, the

number of displayed digits and decimal place

digits is automatically adjusted to 5 digits

regardless of decimal place setting.

Sub Tag settings (INxx_MAIN_TAG)

The Sub Tag is a memo field for making settings

used for entering information (for example, AI1.OUT

or AI1 PV1 and other I/O block information) that is to

be displayed to identify a field instrument in addition

to the information displayed by the Main Tag. Use

INxx_SUB_TAG ( xx: 01 to 16) for setting Sub Tags.

A total of 32 characters can be displayed 14 of

which appear on the screen.

F0704.ai

Figure 7.4 Sub Tag settings

Bar graph setting example

(BAR_GRAPH_SELECT, EACH_BAR_GRAPH)

The bar graph in the lower field on the LCD allows

the user to select either (BAR_GRAPH_SELECT)

to display all IN_xx (xx:01 to 16) or to display

an individual selection of inputs (EACH_BAR_

GRAPH). Bar graphs display upper and lower limit

values according to values scaled using INxx_

SCALE (xx: 01 to 16).

In a batch bar graph setting, setting BAR_GRAPH_

SELECT=0: All are set to inactive will turn off all bar

graph displays and setting 2: All are set to active will

display bar graphs on all screens.

When bar graphs are enabled, the lower display

field will alternately display Sub Tag, communication

status and bar graphs in stated order according to

the interval set by DISPLAY_CYCLE.

Scroll bar display setting (V_SCROLL_BAR)

Use V_SCROLL_BAR to set the scroll bar display

setting. Set V_SCROLL_BAR = 0: Inactive to turn

off the scroll bar display and set it to V_SCROLL_

BAR = 1 Active to have it on at all times. Selecting

V_SCROLL_BAR = 2: Knob link will turn on the

scroll bar display only during display switching and

turns off the display within a few seconds.

F0705.ai

Figure 7.5 Scroll bar settings

Changing scroll direction (SCROLL_

DIRECTION)

The user can change the direction of display

changes made using the scroll knob. Selecting 0:

Turn page clockwise for SCROLL_DIRECTION

increases page numbers (For example: 1/16 а

2/16 а … а 16/16 а 1/16а … when the scroll

knob is turned clockwise). Selecting 1:Turn page

counter-clockwise increase page numbers when

the scroll knob is turned counter-clockwise. 0:Turn

page clockwise is the factory default setting.

Page number information settings (DISP_

PAGE_INFO)

Page number information for process values

indicated by the FVX110 can be displayed in a

minute format. The denominator indicating the total

number of pages is the total number of IN_xx (xx:01

to 16) specified using VALID_CON_SUMMARY

above.

F0706.ai

Figure 7.6 Setting page number information