<2. Handling Cautions>

2-5

IM 01S01C01-01EN

Note: In the rating 1, the output current of the barrier must

be limited by a resistor “Ra” such that Io=Uo/Ra. In the

rating 2 or 3, the output characteristics of the barrier

must be the type of trapezoid which are certified as

the FISCO model (See “FISCO Rules”). The safety

barrier may include a terminator. More than one field

instruments may be connected to the power supply

line.

● FISCO Rules
The FISCO Concept allows the interconnection

of intrinsincally safe apparatus to associated

apparatus not specifically examined in such

combination. The criterion for such interconnection

is that the voltage (Ui), the current (Ii) and the power

(Pi) which intrinsically safe apparatus can receive

and remain intrinsically safe, considering faults,

must be equal or greater than the voltage (Uo,

Voc, Vt), the current (Io, Isc, It) and the power (Po)

which can be provided by the associated apparatus

(supply unit).

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

In addition, the maximum unprotected residual

capacitance (Ci) and inductance (Li) of each

apparatus (other than the terminators) connected to

the fieldbus must be less than or equal to 5 nF and

10 µH respectively.

Ci ≤ 5nF, Li ≤ 10µH

In each I.S. fieldbus segment only one active

source, normally the associated apparatus, is

allowed to provide the necessary power for the

fieldbus system. The allowed voltage(Uo, Voc,Vt)

of the associated apparatus used to supply the

bus cable must be limited to the range of 14 V dc

to 17.5 V dc. All other equipment connected to

the bus cable has to be passive, meaning that the

apparatus is not allowed to provide energy to the

system, except to a leakage current of 50 µA for

each connected device.

Supply unit
Trapezoidal or rectangular output characteristic only

Uo = 14...17.5 V (I.S. maximum value)
Io according to spark test result or other

assessment. No specification of Lo and Co is

required on the certificate or label.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

Loop resistance R': 15...150 Ω/km

Inductance per unit length L': 0.4...1 mH/km

Capacitance per unit length C': 45...200 nF/km.

C'=C' line/line + 0.5 C' line/screen, if both lines

are floating or C'=C' line/line + C' line/screen, if

the screen is connected to one line.

Length of spur cable: max. 60 m

Length of trunk cable: max. 1 km (Group IIC) or

5 km (Group IIB)

Length of splice: max.1m

Terminators
At each end of the trunk cable an FM approved line

terminator with the following parameters is suitable:

R = 90...100 Ω

C = 0...2.2 mF

System evaluations
The number of passive device like transmitters,

actuators, hand held terminals connected to

a single bus segment is not limited due to I.S.

reasons. Furthermore, if the above rules are

respected, the inductance and capacitance of the

cable need not to be considered and will not impair

the intrinsic safety of the installation.

SAFE AREA

HAZARDOUS AREA

F0204.ai

Terminator

(FISCO Model)

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit and

Safety Barrier

(FISCO Model)

Terminator

Data

U

U

I

I.S. fieldbus system complying with FISCO model