A7.5 lm parameters, A7.5.1 lm parameter list, A7.5 – Yokogawa FVX110 User Manual

Page 151: A7-4

Advertising
background image

<Appendix 7. Link Master Functions>

A7-4

IM 01S01C01-01EN

A7.5 LM Parameters

A7.5.1 LM Parameter List

The tables below show LM parameters.

Meanings of Access column entries: RW = read/write possible; R = read only

Index

(SM)

Parameter Name

Sub-parameter Name

(Sub Index)

Default Factory

Setting

Access

Remarks

378 DLME_LINK_MASTER_CAPABILITIES_VARIABLE

0x04

RW

379 DLME_LINK_

MASTER_INFO_

RECORD

0

RW

1 MaxSchedulingOverhead

0

2 DefMinTokenDelegTime

100

3 DefTokenHoldTime

300

4 TargetTokenRotTime

4096

5 LinkMaintTokHoldTime

400

6 TimeDistributionPeriod

5000

7 MaximumInactivityToClaimLasDelay

2

8 LasDatabaseStatusSpduDistributionPeriod 6000

380 PRIMARY_LINK_MASTER_FLAG_VARIABLE

0

RW

LAS: True = 0xFF;

non-LAS: False = 0x00

381 LIVE_LIST_STATUS_ARRAY_VARIABLE

0

R

382 MAX_TOKEN_

HOLD_TIME_

ARRAY

0

RW

1 Element1

0x0000 (×16)

0x012c (×16)

2 Element2

0x012c (×5)

0x0000 (×27)

3 Element3

0x0000 (×32)

4 Element4

0x0000 (×32)

5 Element5

0x0000 (×32)

6 Element6

0x0000 (×32)

7 Element7

0x0000 (×31)

0x012c (×1)

8 Element8

0x012c (×32)

383 BOOT_OPERAT_FUNCTIONAL_CLASS

Specified at the time

of order

RW

0x01 (basic device);

0x02 (LM)

384 CURRENT_LINK_

SETTING_RECORD

0

R

Settings for LAS

1 SlotTime

0

2 PerDlpduPhlOverhead

0

3 MaxResponseDelay

0

4 FirstUnpolledNodeId

0

5 ThisLink

0

6 MinInterPduDelay

0

7 NumConseeUnpolledNodeId

0

8 PreambleExtension

0

9 PostTransGapExtension

0

10 MaxInterChanSignalSkew

0

11 TimeSyncClass

0

385 CONFIGURED_

LINK_SETTING_

RECORD

0

RW

1 SlotTime

12 (0xc)

2 PerDlpduPhlOverhead

4 (0x4)

3 MaxResponseDelay

5 (0x5)

4 FirstUnpolledNodeId

37 (0x25)

5 ThisLink

0 (0x0)

6 MinInterPduDelay

12 (0xc)

7 NumConseeUnpolledNodeId

186 (0xba)

8 PreambleExtension

2 (0x2)

9 PostTransGapExtension

1 (0x1)

10 MaxInterChanSignalSkew

0 (0x0)

11 TimeSyncClass

4 (0x4)

Advertising