A5.3 parameters of pid block, A5.3, A5-2 – Yokogawa FVX110 User Manual

Page 133

Advertising
background image

<Appendix 5. PID Block>

A5-2

IM 01S01C01-01EN

A5.3 Parameters of PID Block

NOTE: In the table below, the Write column shows the modes in which the respective parameters can be

written. A blank in the Write column indicates that the corresponding parameter can be written in all modes of

the PID block. A dash (-) indicates that the corresponding parameter cannot be written in any mode.

Index Index

PID1

Index

PID2

Parameter

Name

Default

(factory setting)

Write

Valid Range

Description

0

8000

8100 Block Header

TAG: “PID”

Block Tag

= O/S

Information on this block such as Block

Tag, DD Revision, Execution Time etc.

1

8001

8101 ST_REV

The revision level of the static data

associated with the function block. The

revision value will be incremented each

time a static parameter value in the

block is changed.

2

8002

8102 TAG_DESC

Null

The user description of the intended

application of the block.

3

8003

8103 STRATEGY

1

The strategy field can be used to

identify grouping of blocks. This data is

not checked or processed by the block.

4

8004

8104 ALERT_KEY

1

1 to 255

The identification number of the plant

unit. This information may be used in

the host for sorting alarms, etc.

5

8005

8105 MODE_BLK

A universal parameter that represents

block operating condition. It comprises

the Actual, Target, Permit and Normal

modes.

6

8006

8106 BLOCK_ERR

This parameter reflects the error

status associated with the hardware or

software components associated with

a block. It is a bit string, so that multiple

errors may be shown.

7

8007

8107 PV

Measured value; the non-dimensional

value that is converted from the input

(IN) value based on the PV_SCALE

values and filtered.

8

8008

8108 SP

0

AUTO

PV_SCALE ±10%

Setpoint

9

8009

8109 OUT

MAN

Output

10

8010

8110 PV_SCALE

100

0

1342

1

O/S

Upper and lower scale limit values used

for scaling of the input (IN) value.

11

8011

8111 OUT_SCALE

100

0

1342

1

O/S

Upper and lower scale limit values used

for scaling of the control output (OUT)

value to the values in the engineering

unit.

12

8012

8112 GRANT_DENY

0

AUTO

Options for controlling access of host

computers and local control panels to

operating, tuning and alarm parameters

of the block.

13

8013

8113 CONTROL_

OPTS

0

O/S

Setting for control action. See Section

A5.13 for details.

14

8014

8114 STATUS_OPTS

0

O/S

See Section A5.15 for details.

15

8015

8115 IN

0

Controlled-value input.

16

8016

8116 PV_FTIME

2

AUTO

Non-negative

Time constant (in seconds) of the first-

order lag filter applied to IN.

17

8017

8117 BYPASS

1 (off)

MAN

1, 2

Whether to bypass the control

computation.

1 (off): Do not bypass.

2 (on): Bypass.

18

8018

8118 CAS_IN

0

Cascade setpoint

19

8019

8119 SP_RATE_DN

+INF

Positive

Rate-of-decrease limit for setpoint (SP).

20

8020

8120 SP_RATE_UP

-INF

Positive

Rate-of-increase limit for setpoint (SP).

21

8021

8121 SP_HI_LIM

100

PV_SCALE ±10%

Upper limit for setpoint (SP).