<Appendix 5. PID Block>

A5-3

IM 01S01C01-01EN

Index Index

PID1

Index

PID2

Parameter

Name

Default

(factory setting)

Write

Valid Range

Description

22

8022

8122 SP_LO_LIM

0

PV_SCALE ±10%

Lower limit for setpoint (SP).

23

8023

8123 GAIN

1

Proportional gain (= 100 / proportional

band).

24

8024

8124 RESET

10

Integration time (seconds).

25

8025

8125 BAL_TIME

0

Positive

Unused

26

8026

8126 RATE

0

Positive

Derivative time (seconds).

27

8027

8127 BKCAL_IN

0

Read-back of control output.

28

8028

8128 OUT_HI_LIM

100

OUT_SCALE ±10% Upper limit for control output (OUT).

29

8029

8129 OUT_LO_LIM

0

OUT_SCALE ±10% Lower limit for control output (OUT).

30

8030

8130 BKCAL_HYS

0.5 (%)

0 to 50%

Hysteresis for release from a limit for

OUT.status.

31

8031

8131 BKCAL_OUT

0

Read-back value to be sent to the

BKCAL_IN in the upper block.

32

8032

8132 RCAS_IN

0

Remote setpoint set from a computer,

etc.

33

8033

8133 ROUT_IN

0

Remote control output value set from a

computer, etc.

34

8034

8134 SHED_OPT

0

Action to be performed in the event of

mode shedding.

SHED_OPT defines the changes to

be made to MODE.BLK.target and

MODE.BLK.actual when the value of

RCAS_IN.status or ROUT_IN.status

becomes Bad if MODE_BLK.actual =

RCas or ROut.

See Section A5.17.1 for details.

35

8035

8135 RCAS_OUT

0

Remote setpoint sent to a computer,

etc.

36

8036

8136 ROUT_OUT

0

Remote control output value.

37

8037

8137 TRK_SCALE

100

0

1342

1

MAN

Upper and lower scale limits used

to convert the output tracking value

(TRK_VAL) to non-dimensional.

38

8038

8138 TRK_IN_D

0

Switch for output tracking. See Section

A5.12 for details.

39

8039

8139 TRK_VAL

0

Output tracking value (TRK_VAL).

When MODE_BLK.actual = LO, the

value scaled from the TRK_VAL value

is set in OUT.

40

8040

8140 FF_VAL

0

Feedforward input value.

The FF_VAL value is scaled to a

value with the same scale as for OUT,

multiplied by the FF_GAIN value, and

then added to the output of the PID

computation.

41

8041

8141 FF_SCALE

100

0

1342

1

MAN

Scale limits used for converting the

FF_VAL value to a non-dimensional

value.

42

8042

8142 FF_GAIN

0

MAN

Gain for FF_VAL.

43

8043

8143 UPDATE_EVT

This alert is generated by any change

to the static data.

44

8044

8144 BLOCK_ALM

The block alarm is used for all

configuration, hardware, connection

failure or system problems in the block.

The cause of the alert is entered in

the subcode field. The first alert to

become active will set the Active status

in the Status attribute. As soon as the

Unreported status is cleared by the alert

reporting task, another block alert may

be reported without clearing the Active

status, if the subcode has changed.