<Appendix 5. PID Block>

A5-4

IM 01S01C01-01EN

Index Index

PID1

Index

PID2

Parameter

Name

Default

(factory setting)

Write

Valid Range

Description

45

8045

8145 ALARM_SUM

Enable

The current alert status,

unacknowledged states, unreported

states, and disabled states of the

alarms associated with the function

block.

46

8046

8146 ACK_OPTION

0xFFFF

Selection of whether alarms associated

with the block will be automatically

acknowledged.

47

8047

8147 ALARM_HYS

0.5%

0 to 50%

Hysteresis for alarm detection and

resetting to prevent each alarm from

occurring and recovering repeatedly

within a short time.

48

8048

8148 HI_HI_PRI

0

0 to 15

Priority order of HI_HI_ALM alarm.

49

8049

8149 HI_HI_LIM

+INF

PV_SCALE

Setting for HI_HI_ALM alarm.

50

8050

8150 HI_PRI

0

0 to 15

Priority order of HI_ALM alarm.

51

8051

8151 HI_LIM

+INF

PV_SCALE

Setting for HI_ALM alarm.

52

8052

8152 LO_PRI

0

0 to 15

Priority order of LO_ALM alarm.

53

8053

8153 LO_LIM

-INF

PV_SCALE

Setting for LO_ALM alarm.

54

8054

8154 LO_LO_PRI

0

0 to 15

Priority order of LO_LO_ALM alarm.

55

8055

8155 LO_LO_LIM

-INF

PV_SCALE

Setting for LO_LO_ALM alarm.

56

8056

8156 DV_HI_PRI

0

0 to 15

Priority order of DV_HI_ALM alarm.

57

8057

8157 DV_HI_LIM

+INF

Setting for DV_HI_ALM alarm.

58

8058

8158 DV_LO_PRI

0

0 to 15

Priority order of DV_LO_ALM alarm.

59

8059

8159 DV_LO_LIM

-INF

Setting for DV_LO_ALM alarm.

60

8060

8160 HI_HI_ALM

Alarm that is generated when the PV

value has exceeded the HI_HI_LIM

value and whose priority order* is

defined in HI_HI_PRI.

* Priority order: Only one alarm is

generated at a time.

When two or more alarms occur at

the same time, the alarm having the

highest priority order is generated.

When the PV value has decreased

below [HI_HI_LIM - ALM_HYS],

HI_HI_ALM is reset.

61

8061

8161 HI_ALM

As above

62

8062

8162 LO_ALM

As above

Reset when the PV value has

increased above

[LO_LIM + ALM_HYS].

63

8063

8163 LO_LO_ALM

As above

64

8064

8164 DV_HI_ALM

Alarm that is generated when the

value of [PV - SP] has exceeded the

DV_HI_LIM value. Other features are

the same as HI_HI_ALM.

65

8065

8165 DV_LO_ALM

Alarm that is generated when the value

of [PV - SP] has decreased below the

DV_LO_LIM value. Other features are

the same as LO_LO_ALM.