<Appendix 6. Multiple Analog Output (MAO) Block>

A6-2

IM 01S01C01-01EN

Other parameters

FSTATE_VAL1

Value transferred as input 1 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL2

Value transferred as input 2 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL3

Value transferred as input 3 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL4

Value transferred as input 4 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL5

Value transferred as input 5 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL6

Value transferred as input 6 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL7

Value transferred as input 7 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_VAL8

Value transferred as input 8 to LCD Transducer Block during fault state status (optional
setting)

FSTATE_STATUS

List of inputs that have transitioned to a fault state

CHANNEL

A means for theoretically accessing LCD Transducer Block (cannot be set on the FVX110)

The MAO function block of the FVX110 can pass 8 inputs (IN_1 – IN_8) to LCD Transducer Block via

CHANNEL.

However, if an input is in a fault state status, the previous value or a user set value (FSTATE_VAL1 – FSTATE_

VAL8) is passed depending on what options (MO_OPTS) have been set.

A6.2 Block Mode

The block mode is defined by the MODE_BLK parameter.

M

O

D

E_

BL

K

Target

Defines the destination of a mode transition.

Actual

Indicates the current block mode. This varies with input data status and target data.

Permitted

Defines restrictions on the destination of a mode transition. Transitions to modes not defined here
cannot be made.

Normal

It defines regular modes.

The MAO function block can take the following three modes (MODE_BLK Actual).

Support Mode

Role

O/S

Performs configuration changes when the system is shut down.

LO

Enabled inputs enter the fault state status and the previous value or a user set value (FSTATE_
VAL1 – FSTATE_VAL8) is transferred to LCD Transducer Block.

Auto

The block is in automatic operation mode.

The destination of the mode transition can be specified by MODE_BLK target, but the destination of a

transition cannot be set to LO mode.

The MAO function block automatically transitions to LO mode when the FAULT_STATE parameter located in

the Resource Block parameter is 2: Active.