A3-8 – Yokogawa FVX110 User Manual

Page 115

Advertising
background image

<Appendix 3. Input Selector (IS) Block>

A3-8

IM 01S01C01-01EN

When SELECT TYPE is “Maximum”
The IS block selects the input with the maximum value among valid inputs and transmits the value of that input

to OUT. The number of the selected input is transmitted to SELECTED.

IN_1 = 23

SELECT_TYPE = Maximum

STATUS_OPTS

MIN_GOOD = 1

SELECTION

SELECTED = 7

OUT = 32.5

IN_2 = 34.5
IN_3 = 45
IN_4 = 2.34
IN_5 = 23.6
IN_6 = 15.5
IN_7 = 32.5
IN_8 = 27.4

DISABLE_1 = OFF
DISABLE_2 = ON
DISABLE_3 = ON
DISABLE_4 = OFF
DISABLE_5 = OFF
DISABLE_6 = OFF
DISABLE_7 = OFF
DISABLE_8 = OFF

OP_SELECT = 0

FA0306.ai

Figure A3.6 Example (5)

Because DISABLE_2 and DISABLE_3 are ON, IN_2 and IN_3 are disabled, and the IN with the maximum

value among the remaining IN_n is selected for output. In the above example, since IN_7 has the maximum

value among the remaining valid INs, it is output.