A4.5 list of the arithmetic block parameters, A4.5, A4-6 – Yokogawa FVX110 User Manual

Page 129

Advertising
background image

<Appendix 4. Arithmetic (AR) Block>

A4-6

IM 01S01C01-01EN

A4.5 List of the Arithmetic Block Parameters

Relative

Index

Index

AR1

Index

AR2

Parameter

Write

Mode

Valid

Range

Initial

Value

View

Description / Remarks

1 2 3 4

0

17500 17600 BLOCK_

HEADER

O/S

TAG=“AR”

Information relating to this function block, such as

block tag, DD revision, and execution time.

1

17501 17601 ST_REV

0

2 2 2 2 Indicates the revision level of the set parameters

associated with the Arithmetic block. If a setting

is modified, this revision is updated. It is used to

check for parameter changes, etc.

2

17502 17602 TAG_DESC

Null

A universal parameter that stores comments

describing tag information.

3

17503 17603 STRATEGY

1

2 A universal parameter intended for use by a high-

level system to identify function blocks.

4

17504 17604 ALERT_KEY

1-255 1

1 Key information used to identify the location at

which an alert has occurred.

Generally, this parameter is used by a high-level

system to identify specific areas in a plant that are

under the control of specific operators, to separate

necessary alerts only. This is one of the universal

parameters.

5

17505 17605 MODE_BLK

AUTO

4

4

A universal parameter representing the operation

status of the Arithmetic block. It consists of the

Actual, Target, Permit, and Normal modes.

6

17506 17606 BLOCK_

ERR

0

2

2

Indicates the error status relating to the Arithmetic

block.

The bit used by this function block is as follows:

Bit 1: Block Configuration Error

Bit 15: O/S mode

7

17507 17607 PV

0

5

5

The result of a range extension function is

substituted into this.

When viewed from the computing equation, PV is

the main input.

8

17508 17608 OUT

MAN

0

5

5

Block output.

9

17509 17609 PRE_OUT

0

5

5

Always indicates the calculation result. The value is

substituted into OUT in Auto mode.

Indicates PV scaling (for making a memo).

Output scaling for the host (for making a memo).

10

17510 17610 PV_SCALE O/S

100

0

1342

1

11

11

17511 17611 OUT_

RANGE

100

0

1342

1

11

12

17512 17612 GRANT_

DENY

0

2

The parameter used to check if various operations

have been executed. The bits in the GRANT

parameter corresponding to various operations

are set before any of them are executed. After the

operations are complete, the DENY parameter is

checked to find out if any bit corresponding to the

relevant operation has been set. If no bit has been

set, it is evident that the operations have been

executed successfully.

Advertising