IM 01S01C01-01EN

Table 9.2

Field Diagnostic Alert

Indication of FD_*_ACTIVE

Indication of FD_RECOMMEN_ACT

Solution

Electronics failure

Repair electronics

Replace electrical parts e.g. amplifier.

Or contact sales office or service

center.

Sensor/Actuator failure

Repair Sensor/Actuator

Replace mechanics e.g. sensor or

actuator. Or contact sales office or

service center.

Potential failure

Investigate failure

Perform reconfiguration, cleaning,

wiring/connector or electrical board

check.

If alarm still persists, contact sales

office or service center.

Backup function in operation

Repair primary side

Repair primary sensor before backup

sensor fails.

Firmware update error

Retry updating firmware

Retry firmware update. Check cause of

the failure if alarm persists.

Communication configuration error

Configure communication correctly

Correct configuration of

communication.

Non-operating-state

Wait for a while

Wait for a while. Check cause of the

failure if alarm persists.

Calibration warning

Check calibration

Investigate cause of failure and

recalibrate device.

Device configuration error

Configure device correctly

Correct configuration relating to sensor

or actuator.

Function restricted

Confirm the state

Check if this is right state.

Simulation mode

Confirm the state

Check if this is right state.

Manual mode

Confirm the state

Check if this is right state.

Function Block notice

Check Function Block status

Check conditions of function

blocks. In order to avoid alarm from

unused function blocks, configure

RESOURCE2.FD_EXTENDC_MAP_n

(n: 1 to 3) parameter.

Sensor/Actuator out of range

Check specification

Check specification of sensor and

actuator. Or process conditions may be

temporarily non-conforming.

Out of operating limit

Check environment

Check environment specification

of sensor and actuator. Or process

environment may be temporarily non-

conforming.

Temporal decrease of value quality

Check process or peripherals

Check process and peripherals

conditions.

Deterioration estimated by Time Based

Maintenance

Check deterioration

Check if maintenance is required.

Deterioration estimated by Condition

Based Maintenance

Check deterioration

Check if maintenance is required.

Optional function configuration error

Check optional configuration

Check configuration of optional

functions.

Alarm related information

Confirm information

Check the alarm related information.

Process alarm

Check process

Check process conditions.