A3-9 – Yokogawa FVX110 User Manual

Page 116

Advertising
background image

<Appendix 3. Input Selector (IS) Block>

A3-9

IM 01S01C01-01EN

When SELECT TYPE is “Middle”
If there is more than one valid input and the number of such input is an odd number, the value of the middle

input will be transmitted to OUT. If there is an even number of valid inputs, the average of the middle two inputs

is transmitted to OUT. If the average is used for OUT, the block transmits “0” to SELECTED, while it transmits

the number of the input used for the middle for other cases. If the number of valid inputs is 1, it is irrelevant to

selection by “Middle” selector action. The following shows an example of selection by “Middle” selector action.

If there is an even number of valid inputs:

IN_1 = 23

SELECT_TYPE = Middle

STATUS_OPTS

MIN_GOOD = 1

SELECTION

SELECTED = 0

OUT = 19.55

(IN_5+IN_6)/2 = 19.55

IN_2 = 34.5

IN_3 = 45

IN_4 = 2.34

IN_5 = 23.6

IN_6 = 15.5

IN_7 = 32.5

IN_8 = 27.4

DISABLE_1 = ON

DISABLE_2 = ON

DISABLE_3 = OFF
DISABLE_4 = OFF

DISABLE_5 = OFF

DISABLE_6 = OFF
DISABLE_7 = ON

DISABLE_8 = ON

OP_SELECT = 0

FA0307.ai

Figure A3.7 Example (6)

Because DISABLE_1, DISABLE_2, DISABLE_7, and DISABLE_8 are ON, the corresponding IN_1, IN_2,

IN_7, and IN_8 are disabled and the remaining four INs are enabled. Furthermore, because IN_3 has the

maximum value and IN_4 has the minimum value among the valid INs, they are not selected and the average

of IN_5 and IN_6 inputs is output. When the average is selected for OUT, SELECTED is set to “0.”

Advertising