A3-10 – Yokogawa FVX110 User Manual

Page 117

Advertising
background image

<Appendix 3. Input Selector (IS) Block>

A3-10

IM 01S01C01-01EN

If there is an odd number of valid inputs:

IN_1 = 23

SELECT_TYPE = Middle

STATUS_OPTS

MIN_GOOD = 1

SELECTION

SELECTED = 5

OUT = 23.6

IN_2 = 34.5

IN_3 = 45

IN_4 = 2.34

IN_5 = 23.6

IN_6 = 15.5

IN_7 = 32.5

IN_8 = 27.4

DISABLE_1 = OFF

DISABLE_2 = OFF

DISABLE_3 = OFF

DISABLE_4 = OFF

DISABLE_5 = OFF

DISABLE_6 = OFF

DISABLE_7 = OFF

DISABLE_8 = ON

OP_SELECT = 0

FA0308.ai

Figure A3.8 Example (7)

If the number of valid INs is an odd multiple, the IN with the middle value will be output. In the above example,

the IN_5 input having the middle value is output.