<9. In-Process Operation>

9-1

IM 01S01C01-01EN

9. In-Process Operation

This chapter describes the procedure performed

when changing the operation of the function block

of the FVX110 in process.

9.1 Mode Transition

When the function block mode is changed to

Out_Of_Service, the function block pauses and a

block alarm is issued.

9.2 Generation of Alarm

9.2.1 Indication of Alarm

The self-diagnostics function of the FVX110 uses

the display to notify the user of the following three

faults.

• The Resource block is in O/S mode

• The MAO1 block is in O/S mode

• The MAO2 block is in O/S mode

The display will then indicate FVX RB OOS,

FVX MAO1 OOS, or FVX MAO2 OOS.

F0901.ai

Figure 9.1 Error identification on indicator (when

MAO1 block is in O/S mode)

When process value have transferred correctly

from field instruments, the ● icon at the center part

of the display flashes. When they are not correctly

transferred, the ● icon is off and the process value

will be highlighted.

F0902.ai

Figure 9.2 Example showing when process value

have correctly transferred

F0903.ai

Figure 9.3 Example showing when process value

have not correctly transferred

The ● icon is not displayed during simulation.

9.2.2 Alarms and Events

The following alarms or events can be reported by

the FVX110 if Link object and VCR static entry are

set.
Analog Alerts (Generated when a process value

exceeds threshold)

By PID Block Hi-Hi Alarm, Hi Alarm, Low

Alarm, Low-Low Alarm. Deviation - Hi Alarm,

Deviation -Low Alarm.

Discret Alerts (Generated when an abnormal

condition is detected)

By Resource Block Block Alarm, Write Alarm

By Transducer Block Block Alarm

By MAO, SC, IT, IS, AR and PID Blocks

Block Alarm

Update Alerts (Generated when an important

(restorable) parameter is updated)

By Resource Block Update Event

By Transducer Block Update Event

By MAO, SC, IT, IS, AR and PID Blocks

Update Event

Field Diagnostic Alerts (Generated when an

abnormal condition in field device is detected)

By Resource Block Check Alarm, Failure

Alarm, Maintenance Alarm, and off

specification Alarm.