2 lcd transducer block, Lcd transducer block -4 – Yokogawa FVX110 User Manual

Page 77

Advertising
background image

<12. Parameter Lists>

12-4

IM 01S01C01-01EN

Relative

Index Index

Parameter Name

Factory Default Write

Mode

Explanation

86

1086 FD_CHECK_PRI

0

AUTO

Indicates the FD_CHECK_ALM priority for an alarm.

87

1087 FD_SIMULATE

AUTO

A parameter for simulating an alarm.

88

1088 FD_RECOMMEN_ACT

0

Indicates procedures for handling essential alarms.

89

1089 FD_EXTENDED_ACTIVE_1 0

A parameter serving as a starting point for alarms handled by

FF-912.

90

1090 FD_EXTENDED_ACTIVE_2 0

A parameter serving as a starting point for alarms handled by

FF-912.

91

1091 FD_EXTENDED_ACTIVE_3 0

A parameter serving as a starting point for alarms handled by

FF-912.

92

1092 FD_EXTENDED_ACTIVE_4 0

Not used by the FVX110.

93

1093 FD_EXTENDED_ACTIVE_5 0

Not used by the FVX110.

94

1094 FD_EXTENDED_ACTIVE_6 0

Not used by the FVX110.

95

1095 FD_EXTENDED_ACTIVE_7 0

Not used by the FVX110.

96

1096 FD_EXTENDED_ACTIVE_8 0

Not used by the FVX110.

97

1097 FD_EXTENDED_MAP_1 0x0748FFFF

AUTO

A parameter set by the user as a mask from DEVICE_

STATUS_1 to FD_EXTENDED_ACTIVE_1.

98

1098 FD_EXTENDED_MAP_2 0xE000EEEE

AUTO

A parameter set by the user as a mask from DEVICE_

STATUS_2 to FD_EXTENDED_ACTIVE_2.

99

1099 FD_EXTENDED_MAP_3 0xFF0EF8FF

AUTO

A parameter set by the user as a mask from DEVICE_

STATUS_3 to FD_EXTENDED_ACTIVE_3.

100

1100 FD_EXTENDED_MAP_4

AUTO

Not used by the FVX110.

101

1101 FD_EXTENDED_MAP_5

AUTO

Not used by the FVX110.

102

1102 FD_EXTENDED_MAP_6

AUTO

Not used by the FVX110.

103

1103 FD_EXTENDED_MAP_7

AUTO

Not used by the FVX110.

104

1104 FD_EXTENDED_MAP_8

AUTO

Not used by the FVX110.

105

1105 PRIVATE_1

Not used by the FVX110.

106

1106 PRIVATE_2

Not used by the FVX110.

107

1107 PRIVATE_3

Not used by the FVX110.

108

1108 PRIVATE_4

Not used by the FVX110.

109

1109 PRIVATE_5

Not used by the FVX110.

110

1110 PRIVATE_6

Not used by the FVX110.

111

1111 PRIVATE_7

Not used by the FVX110.

112

1112 PRIVATE_8

Not used by the FVX110.

113

1113 PRIVATE_9

Not used by the FVX110.

114

1114 PRIVATE_10

Not used by the FVX110.

115

1115 PRIVATE_11

Not used by the FVX110.

12.2 LCD Transducer Block

Relative

Index Index

Parameter Name

Factory Default Write

Mode

Explanation

0

2000 Block Header

TAG : "LTB"

"Block

Tag

=O/S"

Information on this block such as Block Tag, DD Revision,

Execution Time, etc.

1

2001 ST_REV

-

AUTO

Describes the revision level of parameters for setting the

transducer block. The revision is updated when set values

are changed. This parameter is used to check for parameter

changes.

2

2002 TAG_DESC

Null

AUTO

A universal parameter intended for storing comments describ-

ing tag data.

3

2003 STRATEGY

1

AUTO

A universal parameter used by the high-level system to iden-

tify function blocks.

4

2004 ALERT_KEY

1

AUTO

Key information used to identify the location at which an alert

occurred. Generally, this parameter is used by a high-level

system to identify specific areas in a plant that are under the

control of specific operators to distinguish necessary alarms

only. This is a universal parameter.

Advertising