<6. Configuration>

6-6

IM 01S01C01-01EN

Table 6.5

VCR List

Index

(SM)

VCR

Number

Factory Setting

303

1

For system management (Fixed)

304

2

Server (LocalAddr = 0xF3)

305

3

Server (LocalAddr = 0xF4)

306

4

Server (LocalAddr = 0xF7)

307

5

Trend Source (LocalAddr = 0x07,

Remote Address=0x111)

308

6

Publisher for PID1 (LocalAddr =

0x20)

309

7

Alert Source (LocalAddr = 0x07,

Remote Address=0x110)

310

8

Server (LocalAddr = 0xF9)

311

9

Publisher for PID2 (LocalAddr =

0x21)

312 to

337

10 to 35 Not used.

6.5.2 Function Block Execution Control

According to the instructions given in Section 6.3,

set the execution cycle of the function blocks and

schedule of execution.

6.6 Block Setting

Set the parameter for function block VFD.

6.6.1 Link Object

A link object combines the data voluntarily sent by

the function block with the VCR. The FVX110 has

40 link objects. A single link object specifies one

combination. Each link object has the parameters

listed in Table 6.6. Parameters must be changed

together for each VCR because the modifications

made to each parameter may cause inconsistent

operation.

Table 6.6

Link Object Parameters

Sub-

index

Parameter

Description

1

LocalIndex

Sets the index of function

block parameters to be

combined; set “0” for Trend

and Alert.

2

VcrNumber

Sets the index of VCR to be

combined. If set to “0”, this

link object is not used.

3

RemoteIndex

Not used in FVX110. Set

to “0”.

4

ServiceOperation Set one of the following.

Set only one each for link

object for Alert or Trend.

0: Undefined

2: Publisher

3: Subscriber

6: Alert

7: Trend

5

StaleCountLimit

Set the maximum number

of consecutive stale input

values which may be

received before the input

status is set to BAD. To

avoid the unnecessary

mode transition caused

when the data is not

correctly received by

subscriber, set this

parameter to “2” or more.