Maximum input voltage:

DC voltage at 1-V range or less, thermocouple, RTD, and
DI (contact): ±10 VDC (continuous)

Other measurement ranges: ±120 VDC (continuous)

Normal-mode voltage:

DC voltage, thermocouple, DI (LEVEL): 1.2 times the range rating
or less (50/60 Hz, peak value including the signal component)

RTD 100 Ω: 50 mV peak

RTD 10 Ω, 25 Ω, 50 Ω: 10 mV peak

Normal-mode rejection ratio:

For integration time of 16.67 ms or more: 40 dB or more (50/60
Hz ±0.1%)

For integration time of 1.67 ms: 50/60 Hz is not rejected

The RTD ranges indicate the voltage conversion value when
measurement current applied.

Common-mode voltage:

600 VACrms (50/60 Hz), reinforced (double) insulation

Common-mode rejection ratio:

The RTD ranges indicate the voltage conversion value when
measurement current applied.

For integration time is 16.67 ms or more: 120 dB or more

For integration time is 1.67 ms or more: 80 dB or more

(50/60 Hz ±0.1%, 500 Ω unbalanced, between the minus terminal
and ground)

Common-mode voltage between channels (Maximum noise voltage between channels):

120 VACrms (50/60 Hz)

Noise rejection:

Rejection by the integrating A/D converter and the use of low pass
filters

Input resistance:

DC voltage at 1 V range or less, thermocouple range: 10 MΩ or more

DC voltage at 2 V range or more: Approx. 1 MΩ

Insulation resistance: 20 MΩ or more (500 VDC) between the input and ground
Input bias current:

10 nA or less (except for burnout setting)

Withstand voltage:

1000 VAC (50/60 Hz) for one minute between input terminals

3700 VAC (50/60 Hz) for one minute between the input terminal
and earth terminal

Input signal source resistance:

DC voltage and thermocouple: 2 kΩ or less

RTD 50 Ω and 100 Ω systems: 10 Ω or less per cable

RTD 10 Ω and 25 Ω systems: 1 Ω or less per cable

Thermocouple burnout:

Detection at a specified detection interval per measurement
interval and detection within the thermocouple range (detection
ON/OFF possible)

Up/Down setting is possible

2 kΩ or less: normal, 200 kΩ or more: line broken

(Shunt capacity of 0.01 µF or less), detection current of
approximately 10 µA, and detection time of approximately 2 ms

Shunt capacity during RTD: 0.01 µF or less
Power consumption: Approximately 1.2 W
External dimensions: Approximately 57 (W) × 131 (H) × 151 (D) mm (including the

terminal cover)

Weight:

Approximately 0.5 kg

Terminal type:

Clamp, terminal board is detachable

Applicable wire size: 0.14 to 1.5 mm

2

(AWG26 to 16)

4.5 10-CH, Medium-Speed Universal Input Module (MX110-UNV-M10) Specifications