Wiring the digital input modules (-d05, -d24), Wiring the digital input modules (-d05, -d24) -16 – Yokogawa PC-Based MX100 User Manual

Page 61

Advertising
background image

2-16

IM MX100-01E

Wiring the Digital Input Modules (-D05, -D24)

Note

• With the digital input module, the (–) terminal and unassigned terminals on all channels are

shorted internally.

• When the screw terminal plate (model 772080) is connected to the digital input module, the

terminal arrangement differs from that of clamp terminals, therefore wire according to the
markings on the terminal cover.

Wiring with the -D05 Option

• Transistor input

• Contact input

• 5V logic input

Main Input Specifications (-D05)

Input type:

DI (non-voltage contact, open collector, and 5 V logic)

Input format:

Pull-up at approximately 5 V/approximately 5 kΩ, common
electric potential between channels

Min. detection pulse width:

Twice the sampling interval or more

Input threshold level:

Non-voltage contact, open collector: ON at 100 Ω or less and
OFF at 100 kΩ or greater

5-V logic: OFF at 1 V or less and ON at 3 V or greater

Contact/transistor rating:

Contact with a rating of 15 VDC or greater and 30 mA or
greater

Vce and Ic are transistors with ratings of 15 VDC or more, and
30 mA or more, respectively.

Terminal type:

Clamp

Applicable wire size: 0.14 to 1.5 mm

2

(AWG26 to 16)

Wiring with the -D24 Option

24V

• 24 V logic input

Main Input Specifications (-D24)

Input type:

DI (24 V logic)

Input format:

Common potential between ch

Min. detection pulse width:

Twice the sampling interval or more

Input threshold level: 24 V logic: OFF at 6 V or less and ON at 16 V or greater
Terminal type:

Clamp

Applicable wire size: 0.14 to 1.5 mm

2

(AWG26 to 16)

2.4 Connecting the Signal Wires

Advertising