Measurement interval, Filters, Measurement interval -27 filters -27 – Yokogawa PC-Based MX100 User Manual

Page 36: Index

Advertising
background image

1-27

IM MX100-01E

Explanation of Functions

3

2

1

4

5

Index

1.8 Functions of the 10-CH, High-Speed Digital

Input Module (-D05, -D24)

The -D05 module is equipped with ten inputs and measures non-voltage contact, open
collector, and 5-V logic inputs at a minimum measurement interval of 10 ms.
The -D24 module is equipped with ten inputs and measures 24 V logic inputs at a
minimum measurement interval of 10 ms.

Input terminal (clamp terminal)

Terminal cover

Measurement Interval

You can select a measurement interval of 10 ms, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s,
5 s, 10 s, 20 s, 30 s, or 60 s.

Filters

The module detects ON/OFF as shown below to prevent receiving chattering effects. If
the measurement interval is set at a value greater than four times the chattering period,
measurement is possible in which chattering effects are avoided.
• Measurement interval of 5 s or less: Use the wider of the ON/OFF widths of the

detection period (approximately 75 to 90% of the measurement interval)

Detection

interval

Measurement

interval

Detection

interval

Measurement

interval

Measurement

interval

Detection

interval

Detection interval =

Measurement interval × 75% to 90%

Chattering

• Measurement interval of 5 s or more: Use the wider of the ON/OFF width of

approximately 4.5 s

Advertising