Output span setting, Handling abnormal data, Span setting data when setting transmission output – Yokogawa PC-Based MX100 User Manual

Page 116

Advertising
background image

4-28

IM MX100-01E

Setting Value of Span and Preset, and Specified Value of User Output

Analog output setting value

span and preset value

Specified Value of User Output

(count)

Voltage

Current

–11.000 V

0.000 mA

–22000

–10.000 V

0.000 mA

–20000

0.000 V

0.000 mA

0

1.000 V

4.000 mA

2000

5.000 V

20.000 mA

10000

5.500 V

22.000 mA

11000

10.000 V

25.000 mA*

20000

11.000 V

25.000 mA*

22000

*

Value in calculation. Actually, the value is clipped at approximately 22 mA.

Output Span Setting

Span setting data when setting transmission output

• V mode

Output voltage [V]

–10.000

10.000

PC data*

–10000

10000

*

PC data refers to internal data between the PC and MX100 main unit, and on the PC

software, the output value is expressed in the same manner with 3 digits after the decimal

point.

• mA mode

Output voltage [mA] 0.000

20.000

PC data*

0

20000

*

PC data refers to internal data between the PC and MX100 main unit, and on the PC

software, the output value is expressed in the same manner with 3 digits after the decimal

point.

• Limit value of V mode and mA mode

Mode

Output

lower limit

*1

Setting span

lower limit

Setting span

upper limit

Output

upper limit

*2

V mode

–11 [V]

–10 [V]

+10 [V]

+11 [V]

mA mode

0 [mA]

0 [mA]

20 [mA]

22 [mA]

*1 –OVER, preset value
*2 +OVER, preset value

Handling Abnormal Data

Types of Abnormal Data

Output Values

Output data upon startup

Preset value or previously held value can be selected

Data upon error occurrence

Preset value or previously held value can be selected

+OVER

5% of output Full Span

–OVER

–5% of output Full Span

±OVER determination
For user output, ±OVER determination is performed on the PC, and if the limit value is

exceeded, it is clipped at that limit value. For transmission output within the same unit,
OVER is determined by the MX100 main unit.

±OVER conditions
• When the input channel is ±OVER in the case of transmission output
• When outside the range of ±5% of output Full Span
• When outside the range of voltge –11 V to +11 V, or current 0 mA to 22 mA (accuracy

assured at 1 mA or more)

4.10 8-CH, Medium-Speed Analog Output Module (MX120-VAO-M08) Specifications