1.4 Functions of the 10-CH, Medium-Speed

Universal Input Module

This module is equipped with ten inputs and measures DC voltage, Thermocouple, three-
wire RTD, and digital input (DI) at a minimum measurement interval of 100 ms.

Input terminal (clamp terminal)

Terminal cover

Input Type and Measurement Range

The following measurements are possible.

Input

Measurement Range Type

Rated Measurement Range

DC voltage

20 mV

–20.000 to 20.000 mV

60 mV

–60.00 to 60.00 mV

200 mV

–200.00 to 200.00 mV

2 V

–2.0000 to 2.0000 V

6 V

–6.000 to 6.000 V

20 V

–20.000 to 20.000 V

100 V

–100.00 to 100.00 V

Thermocouple

R

0.0 to 1760.0°C

S
B

0.0 to 1820.0°C

K

–200.0 to 1370.0°C

E

–200.0 to 800.0°C

J

–200.0 to 1100.0°C

T

–200.0 to 400.0°C

N

0.0 to 1300.0°C

W

0.0 to 2315.0°C

L

–200.0 to 900.0°C

U

–200.0 to 400.0°C

KPvsAu7Fe

0.0 to 300.0K

RTD

(Measurement current: 1 mA)

Pt100

–200.0 to 600.0°C

JPt100

–200.0 to 550.0°C

Pt100 (high resolution)

–140.00 to 150.00°C

JPt100 (high resolution)

–140.00 to 150.00°C

Ni100 SAMA

–200.0 to 250.0°C

Ni100 DIN

–60.0 to 180.0°C

Ni120

–70.0 to 200.0°C

Pt50

–200.0 to 550.0°C

Cu10 GE

–200.0 to 300.0°C

Cu10 L&N

–200.0 to 300.0°C

Cu10 WEED

–200.0 to 300.0°C

Cu10 BAILEY

–200.0 to 300.0°C

J263B

0.0 to 300.0K

DI

Level

Vth = 2.4 V

Contact input

ON: 1 kΩ or less,

OFF: 100 kΩ or more

(parallel capacitance: 0.01 µF

or less)