Steady output operation, Steady output operation -32, Output operation while communication is connected – Yokogawa PC-Based MX100 User Manual

Page 41

Advertising
background image

1-32

IM MX100-01E

Steady Output Operation

Output Operation While Communication Is Connected

Communication Connection Status

Output Operation

Comm. connects (initial connection after power ON)

Operation upon startup

Comm. connects

Holds the output value (last output value)

(disconnected and restored for the 2nd or more time)
Communication disconnected normally

Holds the output value (last output value)

Output Operation according to the Measurement Status and Transmission
Output Status

Transmission output in the table is ON when Transmission output is selected in the
Action menu of the MX100 Standard Software, or when DAQMXTRANSMIT_RUN is
executed in the MX100/DARWIN API. Transmission output in the table is OFF when
Transmission output is cleared in the Action menu of the MX100 Standard Software, or
when DAQMXTRANSMIT_STOP is executed in the MX100/DARWIN API.

Output Setting Status

Output Operation

Trans. output

Meas stop → meas. start

Starts trans. output/holds within

within units

units output value (depends on

trans. output execution on/off )

on: transmission output starts

off: holds output value

Measuring → meas. stop

Holds output value

(last output value)

Meas stopping Trans. output exec. on* → off* Holds output val. (no change.)

Trans. output exec on → off

Holds output val. (no change.)

Measuring

Trans. output exec off → on

Starts trans. output

Trans. output exec on → off

Holds output val. (last val.)

Trans. output

Meas stop → meas start

Starts user output or holds

between units

output value (depends on trans

(user output)

output exec. on/off status)

on: transmission output starts

off: output value held

Measuring → meas stop

Holds output value

(last output value)

Meas stopping Trans. output exec off → on

Holds output val. (no change.)

Trans. output exec on → off

Holds output val. (no change.)

Measuring

Trans. output exec off → on

User output

Trans. output exec on → off

Holds output val. (last output value)

Manual output

Meas stop → meas start

No effect

(user output)

Measuring → meas stop

No effect

Meas stopping Trans. output exec off → on

No effect

Trans. output exec on → off

No effect

Measuring

Trans. output exec off → on

No effect

Trans. output exec on → off

No effect

Pattern output

Meas stop → meas start

No effect

(user output)

Measuring → meas stop

No effect

Meas stopping Trans. output exec off → on

No effect

Trans. output exec on → off

No effect

Measuring

Trans. output exec off → on

No effect

Trans. output exec on → off

No effect

* on: enabled off: disabled

Transmission output execute enabled: when “Transmit” under the Action menu of the PC

software is selected

Transmission output execute disabled: when “Transmit” under the Action menu of the PC

software is not selected

1.11 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output

Module