Index, Output operation per setting changes (common) – Yokogawa PC-Based MX100 User Manual

Page 40

Advertising
background image

1-31

IM MX100-01E

Explanation of Functions

3

2

1

4

5

Index

Output Operation per Setting Changes (Common)

Setting Changes (Contents)

Output Operation

Changes to settings for op.

Hold prev. val. → preset val. Outputs a preset value the next

time upon startup the power is

turned ON

Preset val. → hold prev. val. The last output value from the

previous operation is held for the

next time the power is turned ON

(outputs the output value active when

the power was last turned OFF

during the previous session)

Changes to settings for op.

Hold prev. val. → preset val. Outputs a preset value the next

time when error occurs an error

occurs

Preset val → hold prev. val. Holds the last output value active

before an error occurs even when the

next error occurs.

Changes to the preset value setting*

No change (as above)

Output ch setting changed from Enabled → Disabled

Holds the output val. (last output val.)

* Changes are also applied to inactive channels.

Output Operation through Setting Changes (Individually by Output Setting)

Output

Setting Changes (Contents)

Output Operation

Setting
Trans. output Range setting chng. AO: V↔ mA

Output value held

within units

PWM: 1 ms ↔10 ms or interval

(until next output event)

Op. setting chng.

Trans. within units → Trans. between

units

Trans. within units → manual output

Trans. within units → pattern output

Trans. output Range setting chng. AO: V ↔ mA

Output value held

between units

PWM: 1 ms ↔10 ms or interval

(until next output event)

(user output) Op. setting chng.

Trans. between units → trans. within

units

Trans. between units → manual output

Trans. between units → pattern output

Manual output Range setting chng. AO: V ↔ mA

Output value held

(user output)

PWM: 1 ms ↔10 ms or interval

(until next output event)

Op. setting chng.

Manual output → trans. within units

Manual output → trans. between units

Manual output → pattern output

Span setting changes

Pattern output Range setting chng. AO: V ↔ mA

Output value held

(user output)

PWM: 1 ms ↔10 ms or interval

(until next output event)

Op. setting changes Pattern output → trans. within units

Pattern output → trans. between units

Pattern output → manual output

Span setting changes

If the PWM output module range setting is changed, the output value is not saved (the interval
changes)

1.11 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output

Module