Wiring the analog output modules, Wiring the pwm output modules, Index wiring the analog output modules – Yokogawa PC-Based MX100 User Manual

Page 62: Caution

Advertising
background image

2-17

IM MX100-01E

Installation and W

iring

3

2

1

4

5

Index

Wiring the Analog Output Modules

External power supply

Voltage

V+

Load

+ 24 V

power supply

(when using current output)

Direction of

current

Vext

Current

I+

Load

CAUTION

Two power supply terminals are connected internally. Therefore, do not connect a
separate external power supply to them as fire can result.

Main Output Specifications

Terminal type:

Clamp, attached and removed in units of 4 channels

Load impedance:

Voltage 5 kΩ or more

Current 600 Ω or less

Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

Wiring the PWM Output Modules

External power supply

Pulse width output

V+

Load

+

4-28 V

power supply

CAUTION

Two power supply terminals are connected internally. Therefore, do not connect a
separate external power supply to them as fire can result.

Main Output Specifications

Output capacity:

1A/ch max, however, 4 A or less total for all modules

*1, *2

Terminal type:

Clamp, attached and removed in units of 4 channels

Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

*1 A 1A current limit circuit is built in to the output circuit. Once the current limit circuit is ON,

the circuit continues to operate unless the external power supply is turned OFF.

*2 This module has a built-in fuse. The built-in fuse protects against fires or abnormal

emissions of heat due to load short-circuiting or other abnormalities.

2.4 Connecting the Signal Wires