Index, External dimensions – Yokogawa PC-Based MX100 User Manual

Page 121

Advertising
background image

4-33

IM MX100-01E

Specification

3

2

1

4

5

Index

4.13 10-CH, Medium-Speed Digital Output Module

(MX125) Specifications

Style number:

S1

Number of outputs:

10

Contact mode:

A contact (SPST)

Update interval:

Output per 100 ms (not synchronized to the measurement
interval)

Contact capacity:

250 VDC/0.1 A, 250 VAC/2 A, or 30 VDC/2A (resistance load)

Contact life*:

100,000 times at rated load (typical)

20,000,000 times at no load (typical)

* The contact life varies depending on the load conditions and the

environment in which it is used.

Insulation resistance: 20 MΩ or more (500 VDC) between output terminal and earth

20 MΩ or more (500 VDC) between the output terminals

Withstand voltage:

2300 VAC (50/60 Hz) for one minute between the output terminal
and earth

2300 VAC (50/60 Hz) for one minute between output terminals

Maximum common-mode voltage:

250 VACrms (50/60 Hz)

Power consumption: Approximately 2 W (when all relays are turned ON)
Terminal type:

Clamp, attached and removed in units of 5 channels

Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

External dimensions: Approx. 57 (W) × 131 (H) × 151 (D) mm (including the terminal

cover)

Weight:

Approximately 0.5 kg

External Dimensions

Unit: mm

57

13

1

150.8

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3

mm.

Advertising