2-20

IM MX100-01E

Wiring the Power Supply Terminal (Power Supply/Cord Basic Specification Code 1W)

WARNING

• Set up a switch on the power supply line that shuts off the main power supply to

the instrument. Also, include an ON/OFF indicator with the switch as well as a
label that identifies the switch as the power shut down switch.

Switch specifications
Steady state current rating: 3 A or more
Inrush current rating: 80 A or more
Conforms with IEC60947-1 and -3
• Connect a fuse of 2 A to 15 A to the power supply line.
• Do not insert a switch or fuse on the ground line.

1.

Check that the power switches to the power supply and main module are turned

OFF.

2.

Loosen the power terminal cover attachment screws on the main module and

open the terminal cover.

3.

Wire the power supply cord and protective grounding cord to the power supply

terminal as shown in the figure below.

Use round crimp-on lugs with isolation sleeves (for 4 mm screws) for the power cord and
protective ground cord terminals.

4.

Close the power supply terminal cover and secure it with the screw.

Power cord

Protective grounding cord

Power supply terminal cover

Protective grounding cord

Power cord

crimp-on lugs

with isolation

sleeves

L N

2.5 Power Connection and ON/OFF