Partially-Filled Pipe Situations

In some locations, the process pipe may be momentarily only partially filled Examples include: lack of back pressure,

insufficient line pressure and gravity flow applications
To eliminate these situations, do not install the meter at the highest point of the pipeline

WRONG

FL

OW

Figure 12: Incorrect Meter Placement

Do not install the meter in a vertical, downward flow section of pipe
Always position the ON/OFF valves on the downstream side of the meter

WRONG

RIGHT

FL

OW

FL

OW

FL

OW

WRONG

FL

OW

RIGHT

WRONG

RIGHT

FL

OW

FL

OW

FL

OW

WRONG

FL

OW

RIGHT

Do not install in a vertical, downward position

Position "On/Off" valves on downstream side

Figure 13: Position Valves on Downstream Side

To minimize the possibility of partially-full pipe flows in horizontal, gravity or low pressure applications, create a pipe

arrangement that ensures the detector remains full of liquid at all times

Figure 14: Pipe Positioned to Keep Water in Detector

M-Series® M2000 Electromagnetic Flow Meter

Page 12

August 2012