External Disconnect

Install an external disconnect switch or circuit breaker that meets local standards

Position the M2000 in an accessible location

Position and identify the disconnect device so as to provide safe and easy operation

Label the disconnect device as being for the mag meter

AC Power Wiring

For the AC power connections, use three wire-sheathed cable with an overall cable diameter of 0 2…0 45 inch (5…12 mm)

For signal output, use 18…22 gauge (0 25…0 75 mm

2

) shielded wire Overall cable diameter between 0 12…0 35 inch

(3…9 mm)

To prevent accidents, connect main power only after all other wiring has been completed

The amplifier is a microprocessor device It is important that the power supply be as “clean” as possible Avoid using power

lines that feed heavy loads: pumps, motors, etc. If dedicated lines are not available, a filtering or isolation system may be

required
Power wiring is the same for meter mount and remote mount amplifiers

Remote Mount Installation

If you are installing the M2000 amplifier in a remote location, review the procedures in this section

Mount Bracket to Amplifier

1 Align bracket-mounting holes with amplifier mounting holes
2 Attach bracket to amplifier with supplied screws Torque screws to 80 inch pounds

Wiring Configuration

Wiring between the detector and the M2000 amplifier comes complete from the factory If your installation requires the use

of conduit, we recommend that you follow these steps when wiring the detector to the amplifier

1 Remove the junction box lid Carefully remove the wires connected to the terminal blocks that run to the M2000

amplifier See the chart below for a reference of wire color to terminal connection

2 Run cable through the conduit from the amplifier location while retaining the wiring of the cable to the amplifier, as

supplied

3 Complete conduit assembly on both ends and rewire the cable into the junction box as it was previously wired

M-Series® M2000 Electromagnetic Flow Meter