Measurements

Low Flow Cutoff

[0 2%]

U

Low flow cutoff defines the threshold at which flow measurement will be forced to zero The cutoff

value can be set from 0% to 10% of the full scale flow Increasing this threshold will help prevent false

readings during “no flow” conditions possibly caused by pipe vibration or inherent system noise
To change the Low Flow Cutoff value, follow these steps from the Measurements menu:

1 Select Low Flow Cutoff to view the Low Flow Cutoff display
2 Set the low flow cutoff value to the desired setting
3 Press [E] to save the new low flow cutoff value

Flow Direction

[Bi-Directional]

U

Flow Direction lets you set the meter to measure forward flow only (uni-directional) or both forward and

reverse flow (bi-directional)

Uni-Directional

Flow is totalized in only one direction The flow direction is indicated by the arrow printed on the

detector label Uni-directional measurements on the main display screen include:

T1: Registers forward flow, resettable by menu or MODBUS RTU

T2: Registers forward flow, resettable by menu, MODBUS RTU, or digital input configured for

Remote Reset

Bi-Directional

Flow is totalized in both directions Bi-directional measurements on the main display screen include:

T+: Registers forward flow, resettable by menu or MODBUS RTU

T–: Registers reverse flow, resettable by menu or MODBUS RTU

TN: Registers total flow, T+ – T–, resettable by menu or MODBUS RTU

To change the flow direction follow these steps from the Measurements menu

1 Select Flow Direction to view the Flow Direction display
2 Select Uni-Directional or Bi-Directional
3 Press [E] to save the flow direction and return to the Measurements menu

Damping Factor

[No Damping]

U

The damping factor establishes the stability of the measured flow rate If back and forth oscillations of

the flow rate are observed during normal flow conditions, increase this value incrementally until the

flow rate stabilizes This parameter has no affect on the totalizers
To change the Damping Factor value, follow these steps from the Measurements menu

1 Select Damping Factor to view the Damping Factor display
2 Select one of the following damping factors:

1 Second

10 Seconds

2 Seconds

20 Seconds

3 Seconds

30 Seconds

4 Seconds

No Dampening

5 Seconds

3 Press [E] to save the damping factor and return to the Measurements menu

Installation & Operation Manual