ADE INTERFACE

This feature requires firmware version 1 10 or later Reference Badger Meter P/N 6734-003 to obtain a firmware upgrade kit

Enabling the meter as an ADE register requires three settings, all within the advanced menu, to be configured

Unit Multiplier – Selects the resolution of the display totalizer

Protocol Type – Selects the type of information to be transmitted to the ADE transmitter

Dial Type – Enables ADE and selects the number of significant totalizer digits to transmit

Changing the dial type from Disabled will automatically configure the necessary digital inputs/outputs It is not allowed to

manually change the digital inputs/outputs within the Input/Outputs menu

Below is a wiring diagram for connecting an ADE

transmitter to the meter

ADT Connections

1

2

3

4

5

6

7

8

9

10

11

12

13

14

IMPNROANOE: Remove jumper

JP1 before connecting transmitter

to meter

JP1

RED = CLOCK

GREEN = DATA

BLACK = GND

ADE Transmitter Cable

Output #1

COM

Input

Figure 20: ADE Interface

M-Series® M2000 Electromagnetic Flow Meter