Badger Meter M-Series M2000 User Manual

Page 50

Advertising
background image

Info/Help

Rollover Counts

[0]

U

The number of times the totalizers have rolled over 9,999,999,999 (10 billion)
As the meter rolls over, a status indicator appears in the display When this occurs, we suggest that

you record the totalizers and rollover counter and reset the totalizers Resetting totalizers will also

clear the rollover counter
For a meter configured in bidirectional mode, rollover is represented by the net totalizer (TN) as

“*********” During this condition, the net totalizer (TN) can be calculated using the following

equation:

T(FWD) = [(ROLLOVER

T+

x 10,000,000,000) + T+]

T(REV) = [(ROLLOVER

T-

x 10,000,000,000) + T–]

TN =T(FWD) – T(REV)

Where ROLLOVER

Tx

is the rollover count for the appropriate totalizer

For a meter configured in unidirectional mode, the totalizer can be calculated using the following

equation:

T1 = [(ROLLOVER

T1

x 10,000,000,000) + T1]

T2 = [(ROLLOVER

T2

x 10,000,000,000) + T2]

Where ROLLOVER

Tx

is the rollover count for the appropriate totalizer

PowerUp Counter

[Not applicable]

U

The number of times that the unit has been powered on

Power Off Totalizer

[Not applicable]

U

The length of time that the unit has been without power

Version Info

[Not applicable]

U

The current software version

Serial Number

[Not applicable]

U

The manufacturing serial number in the format YYMM####
Where YYMM indicates year and month of manufacturing and #### indicates the sequence number

M-Series® M2000 Electromagnetic Flow Meter

Page 50

August 2012