Inputs/Outputs

Digital Output

Pulses/Unit
[1]

S

The Pulses/Unit parameter lets you set how many pulses per unit of measure will be

transmitted to remote applications For example, assuming the unit of measure is

gallons:

• Setting the Pulses/Unit to 1 will transmit 1 pulse every gallon
• Setting the Pulses/Unit to 0 01 will transmit 1 pulse every 100 gallons

You must configure pulses/unit if the function of the selected output is to be

forward, reverse or AMR pulse
This parameter must be considered with the Pulse Width and Full Scale Flow

parameters The maximum pulse frequency is 10 kHz The frequency is correlated

with the flow rate Violation of output frequency limits will generate a configuration

error
To change the pulses/unit, follow these steps from the Inputs/Outputs menu:

1 Select Digital Output 1 or 2 and press [E] to open the Digital Output menu
2 From the Digital Output menu select Pulses/Unit, and press [E] to open the

Pulses/Unit display

3 Enter the pulses/unit value Press [E] to save the new parameter and return to

the Digital Output menu

Pulse Width
[0 ms]

S

The Pulse Width parameter establishes the On duration of the transmitted pulse The

configurable range is from 0 to 1000 ms

• Non-zero pulse width configuration – the Off duration of the transmitted pulse

is dependent on flow rate The Off duration is to be at least the configured On

duration At full scale flow, the On duration equals the Off duration The

maximum configurable output frequency is limited to 500 Hz

• 0 ms pulse width configuration – the duty cycle of the transmitted pulse is at 50

percent allowing for a maximum configurable output frequency of 10 kHz

This parameter must be considered with the Pulses/Unit and Full Scale Flow

parameters The maximum pulse frequency is 10 kHz The frequency is correlated

with the flow rate Violation of output frequency limits will generate a configuration

error
To change the pulse width, follow these steps from the Inputs/Outputs menu:

1 Select Digital Output 1 or 2 and press [E] to open the Digital Output menu
2 From the Digital Output menu select Pulse Width, and press [E] to open the

Pulse Width display

3 Enter the pulse width value Press [E] to save the new parameter and return to

the Digital Output menu