SECTION 6 - JLG CONTROL SYSTEM

6-60

– JLG Lift –

3121180

2/2

Flash code 2/2 indicates problems with drive & steer selection. Except
where noted, these faults are not reported during 2 second power-up
sequence.

3

DRIVE LOCKED – JOYSTICK MOVED
BEFORE FOOTSWITCH

Drive selected before and during footswitch closure. Can be reported during
power-up sequence.

FSW INTERLOCK TRIPPED

Footswitch closed for seven seconds with no function selected. Can be
reported during power-up sequence.

STEER LOCKED – SELECTED
BEFORE FOOTSWITCH

Steer was selected before and during footswitch closure.

STEER SWITCHES FAULTY

Both steer switches are active at same time.

D/S JOY. OUT OF RANGE LOW

Resistive joysticks: These faults do not occur.

D/S JOY. OUT OF RANGE LOW

Resistive joysticks: These faults do not occur.

D/S JOY. OUT OF RANGE HIGH

Resistive joysticks: These faults do not occur if Vref voltage is below 8.1 volts. If
Vref is above 7.7 volts, Vref is operating out of tolerance or a short to battery has
occurred.

D/S JOY. CENTER TAP BAD

Resistive joysticks: These faults occur when center tap voltage is not between
3.08 volts and 3.83 volts. Due to resistor tolerances there is a +/-.1 volt range
around these values where fault may be indicated.

WAITING FOR FSW TO BE OPEN

Footswitch closed when platform mode was selected. Can be reported during
power-up sequence.

FOOTSWITCH SELECTED BEFORE
START

User attempted to start machine with footswitch engaged.

2/3

Flash code 2/3 indicates problems with boom function selection.

3

LIFT/SWING LOCKED – JOYSTICK
MOVED BEFORE FOOTSWITCH

Platform upper lift or swing was selected before and during footswitch closure.

PUMP SWITCHES FAULTY – CHECK
DIAGNOSTICS/BOOM

A boom function (lower lift, telescope, basket level, basket rotate, jib) has both
directions selected together.

PUMP SWITCHES LOCKED –
SELECTED BEFORE FOOTSWITCH

A platform boom function (lower lift, telescope, basket level, basket rotate, jib)
was selected before key switch or footswitch closure.

PUMP SWITCHES LOCKED –
SELECTED BEFORE AUX POWER

A ground boom function (lower lift, telescope, basket level, basket rotate, jib)
was selected before aux power.

l/s joy. out of range low

Resistive joysticks: These faults do not occur.

l/s joy. out of range high

Resistive joysticks: These faults do not occur if Vref voltage is below 8.1 volts. If
Vref is above 7.7 volts, Vref is operating out of tolerance or a short to battery has
occurred.

l/s joy. center tap bad

Resistive joysticks: These faults occur when center tap voltage is not between
3.08 volts and 3.83 volts. Due to resistor tolerances there is a +/-.1 volt range
around these values where fault may be indicated.

PUMP SWITCHES LOCKED –
SELECTED BEFORE START SWITCH

Hydraulic function switch closed before start switch closed.

FOOTSWITCH SELECTED BEFORE
START

User attempted to start machine with footswitch engaged.

2/4

Flash code 2/4 indicates steering digital inputs are faulty.
NOT REQUIRED

Table 6-8. Help Fault Codes, Displayed Faults, and Descriptions - S/N 0300066949 & S/N 1300000001 to Present

Fault Flash

Code

Communicated (Displayed on

Analyzer) Fault

Description

Priority