Product description – Lenze I/O system 1000 System Manual User Manual
Page 108

Product description
I/O compound modules − digital I/O
Two relay outputs − EPM−S308
l
108
EDSIO1000 EN 7.0
Technical data
EPM−S308: rated data
Module identifier
265
dec
Current consumption/power loss
Current consumption from backplane bus
130 mA
Power loss
0.7 W
Relay outputs
Number of outputs
2
Load voltage
Nominal value
DC 30 V / AC 230 V
Total current
for each group, horizontal structure,
40°C
3 A
for each group, horizontal structure,
60°C
3 A
for each group, vertical structure
3 A
Output current
for "1" signal, nominal value
3 A
Maximum switching capacity
Service life
Parallel switching of outputs
for redundant control
Not possible
for power increase
Not possible
Control of a digital input
Not possible
Switching frequencies
for ohmic loads
Max. 100 Hz
Output data size
8 bits (with EPM−S110: 2 bits)