Product description – Lenze I/O system 1000 System Manual User Manual
Page 58

Product description
Bus coupler modules
DeviceNet − EPM−S150
l
58
EDSIO1000 EN 7.0
Setting the DeviceNet address:
All stations on the bus must be uniquely identified by means of a DeviceNet address which
is between 0 and 63. Proceed as follows to define the baud rate:
1. Switch off the voltage supply.
2. Set the switch 1 to "0" (address).
3. Set the address via switches 2 ... 4 according to the following table.
DeviceNet address
3
View
Pos.
Valency
Example
Switching
status
Result
"1" "0"
1
8
1
Configuration
0
0: Address setting
2
1
1
1 + 2 + 16 = 19
per address: 19
3
2
1
4
4
0
5
8
0
6
16
1
7
32
0
SLIO004
8
Not assigned
−
4. Switch on the voltage supply.
The set node address is saved in the EEPROM. In case of a wrong or already available
address the SF−LED (red) is lit after PowerON.
Setting the update mode:
Set the update mode to transmit a firmware to the bus coupler.
How to proceed:
1. Switch off the voltage supply.
2. Set the switch 1 to "1" (= baud rate/update mode).
3. Set the update mode via switches 2 ... 4 according to the following table.